background image

SELF

DIAGNOSTICS

 

TESTING:

 

1)

 

Introduction

 

Once

 

the

 

unit

 

is

 

properly

 

installed

 

according

 

to

 

the

 

Installation

 

instruction

 

sheet

 

and

 

AC

 

power

 

is

 

supplied,

 

the

 

EXIT

 

will

 

come

 

ON.

 

The

 

dual

color

 

LED

 

indicator

 

will

 

also

 

come

 

ON,

 

automatically

 

initiating

 

the

 

self

diagnostic

 

test

 

function.

 

The

 

LED

 

indicator

 

points

 

out

 

the

 

current

 

unit

 

status.

 

A

 

STEADY

 

GREEN

 

on

 

the

 

LED

 

indicator

 

indicates

 

a

 

normal

 

service;

 

BLINKING

 

GREEN

 

indicates

 

that

 

the

 

unit

 

is

 

in

 

testing

 

mode;

 

GREEN/RED

 

FLASHING

 

indicates

 

that

 

the

 

battery

 

is

 

charging;

 

RED

 

(STEADY

 

and

 

BLINKING)

 

would

 

indicate

 

a

 

fault

 

or

 

a

 

service

 

alert.

 

Refer

 

to

 

section

 

3

 

 

Fault

 

Indication

 

for

 

more

 

details.

 

The

 

LED

 

indicator

 

would

 

be

 

OFF

 

when

 

the

 

unit

 

is

 

in

 

Emergency

 

mode.

 

2)

 

Self

 

 

Diagnostic

 

Service

 

The

 

self

diagnostic

 

function

 

is

 

factory

 

preset

 

without

 

any

 

field

 

adjustment.

 

The

 

automatic

 

self

diagnostic

 

feature

 

serves

 

the

 

following

 

tests

 

   

a.

 

On

line

 

real

 

time

 

monitoring

 

of

 

battery

 

and

 

lamps:

 

Identifies

 

battery

 

charging,

 

disconnection

 

and

 

failure

 

along

 

with

 

lamp

 

failure.

 

b.

 

Self

testing

 

and

 

a

 

30

second

 

discharge

 

once

 

every

 

30

 

days

 

(conforming

 

to

 

NFPA

 

code

 

requirements),

 

after

 

AC

 

power

 

has

 

been

 

supplied

 

for

 

a

 

minimum

 

of

 

24

 

hours.

 

c.

 

Self

testing

 

and

 

a

 

30

minute

 

discharge

 

once

 

every

 

180

 

days,

 

after

 

AC

 

power

 

has

 

been

 

supplied

 

for

 

a

 

minimum

 

of

 

24

 

hours.

 

d.

 

Self

testing

 

and

 

a

 

90

minute

 

discharge

 

once

 

every

 

365

 

days

 

(conforming

 

to

 

NFPA

 

code

 

requirements),

 

after

 

AC

 

power

 

has

 

been

 

supplied

 

for

 

a

 

minimum

 

of

 

24

 

hours.

 

3)

 

Fault

 

Indication

 

Function

 

LED

 

Indication

 

Unit

 

is

 

in

 

normal

 

mode

 

STEADY

 

Green

 

Battery

 

Disconnected

 

STEADY

 

Red

 

Battery

 

Recharge

 

Red

 

and

 

Green

 

(flashing

 

alternatively)

 

Battery

 

Recharge

 

Failure*

   

FLASHING

 

Red

 

Battery

 

Failure**

   

Red

 

BLINKING

 

‘2’

 

times

 

LAMP

 

Failure

   

Red

 

BLINKING

 

‘4’

 

times

 

Remote

 

LAMP

 

Failure

   

Red

 

BLINKING

 

‘5’

 

times

 

*

 

A

 

battery

 

recharge

 

failure

 

will

 

come

 

up

 

if

 

the

 

battery

 

is

 

NOT

 

able

 

to

 

recharge

 

within

 

the

 

24hrs

 

charging

 

time

 

**

 

A

 

battery

 

failure

 

will

 

come

 

up

 

if

 

the

 

battery

 

is

 

NOT

 

able

 

to

 

operate

 

the

 

lamps

 

for

 

the

 

period

 

of

 

a

 

discharge

 

test

 

4)

 

Manual

 

Testing

 

This

 

unit

 

also

 

provides

 

for

 

manual

 

testing

 

by

 

pushing

 

the

 

test

 

switch

 

in

 

a

 

specific

 

pattern.

 

The

 

different

 

patterns

 

and

 

the

 

resulting

 

tests

 

are

 

listed

 

in

 

the

 

table

 

below.

 

 

ACTION

 

REACTION

 

AND

 

LED

 

INDICATION

 

Push

 

test

 

button

 

once

 

(within

 

2

 

seconds)

 

30

second

 

test;

 

FLASHING

 

Green

 

Push

 

test

 

button

 

‘2’

 

times

 

(within

 

2

 

seconds)

 

30

minute

 

test;

 

Green

 

BLINKING

 

‘2’

 

times

 

Push

 

test

 

button

 

‘3’

 

times

 

(within

 

2

 

seconds)

 

90

minute

 

test;

 

Green

 

BLINKING

 

‘3’

 

times

 

Push

 

&

 

Hold

 

test

 

button

 

(3

5

 

seconds)

 

System

 

Interruption

 

Push

 

&

 

Hold

 

test

 

button

 

(more

 

than

 

6

 

seconds)

 

System

 

Reset

 

5)

 

Operation

 

During

 

an

 

electrical

 

power

 

failure,

 

the

 

lamps

 

will

 

automatically

 

come

 

ON

 

for

 

a

 

minimum

 

of

 

90

 

minutes.

 

To

 

test

 

this

 

unit,

 

the

 

battery

 

needs

 

to

 

be

 

charged

 

initially

 

for

 

2

 

hours

 

before

 

depressing

 

the

 

test

 

switch

 

(to

 

do

 

manual

 

test).

 

On

 

pressing

 

the

 

test

 

switch,

 

the

 

Lamps

 

will

 

illuminate.

 

The

 

Lamps

 

will

 

turn

 

OFF

 

after

 

30

sec

 

/30

min

 

/90

min

 

depending

 

on

 

the

 

number

 

of

 

times

 

the

 

switch

 

has

 

been

 

pressed.

 