background image

Instructions for  LED Emergency Lighting  Fixture

IMPORTANT

IMPORTANT SAFEGUARDS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SAVE THESE  INSTRUCTIONS

FLEXIBLE  CONDUIT  ONLY

INSTALLATION  (J-BOX  MOUNTING)

INSTALLATION  (CONDUIT )

WARNING:

Let the battery charge up for at least 24 hours.Then normal operation of 

this unit should take effect . To check, press the " TEST  " button . The 

LED lamps on the unit should turn ON. During an electrical power failure, 

the led lamps will automatically come on for a minimum of 90 minutes. In 

accordance with NFPA 101, your emergency lighting system must be 

tested monthly for a minimum of 30 seconds and annually for 90 minutes. 

Refer to your local codes for any additional requirements that may apply. 

 

When using electrical equipment, basic safety precautions should always be followed including the following:

1. Do not use outdoors.

2. Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.

3. Do not mount near gas or electric heaters.

4. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

5. Do not use this equipment for anything other than its intended use.

6. Servicing of this equipment should be performed by qualified personnel.

7. Disconnect AC power before servicing.

1. Feed fixture leads through the back plate and connect to AC power supply (Fig A). For 120V use black and white wires and 

    for 277V, use red and white wires.

2. Attach back plate to J-Box and secure with screws.

3. Complete the battery connection. (Fig. B)

4. Align snaps and push housing directly onto the back plate (Fig. C). Apply continuous AC power and press "TEST" button 

    to check light.

1. Secure back plate to wall surface . Route wires through hole in conduit flange and make conduit connection. For 120V,

    use black and white wires and for 277V, use red and white wires.

2. Complete the battery connection (Fig. B).

3. Align snaps and push housing directly onto the back plate (Fig. C).  Apply continuous AC power and press "TEST" button to 

    check light.

Unused wires must be capped using enclosed wire nuts.

Fig.A (J-Box)

Fig.B

Fig.C

BATTERY CONNECTOR

PLUG IN

LED

POWERED! 

Page 1 of 2

Отзывы: