CH Burner OFF Duration:
The boiler stays turned
off for this period when it is turned off at hysteresis. At the
end of this period, if the water temperature drops below
hysteresis opening value, the boiler restarts burning;
however, the boiler is not activated if it does not drop below
that value.
•
CH Pump Overrun Time:
Pump continues to run for
a given period of time after the heat demand.
•
Eco Mode Hysteresis Turn-on Set Value:
P39:1 is the default value. Example: When CH set value
is set at 30°C, no flame is formed before boiler
return water temperature sensor reaches to 27°C.
P39: 0 is an optional parameter.When it is activated,
boiler waits lower temperatures than its normal working
condition to operate again.
Table
6
. Set Values
P39
1
0
Set
Value
CH Return
Water
Temperature
CH Return
Water
Temperature
30
27
22
35
27
22
40
31
26
45
34
29
50
36
31
55
40
35
60
44
39
65
47
42
70
51
46
75
53
48
80
57
52
•
When P43 parameter is selected to reset the ASE
maintenance counter, select “reset” text on the
screen
and
then ASE maintenance counter is reset.
In 0.46 software,
ASE mode was exited by
pressing the reset
button once. In
software 0.56, it is possible to reset of ASE counter from
P43
parameter with a password.
•
In software before 0.56, it is sufficient to press the Reset
button once to exit the ASE mode.
AP Mode:
During this mode ”AP” and water pressure
values will appear on the screen.
•
Accessing to Inquiry Mode (In):
Inquriy Menu;
gives details on the status of the boiler during oeration.
Values of certain data may be checked spontaneously by
accessing this menu.
When “In” is selected by pressing on “B” button in the
menu, “i00” is displayed on screen. It is possible to select
any parameter wished by pressing on DHW(-)(E) and
DHW(+)(C) buttons.
It is possible to select and see value of any
parameter by means of CH(+)(D) and CH(-)(F) buttons.
Any short or open circuit in the sensors are displayed
on screen.
Actual fan speed is always given as rpm/10.
Actual flame current is always given as µAx10
It is possible to go back “In” parameter by pressing
on “B” (RESET) button for 1 second; after that,
pressing on “A” button again takes you out of the inqury
mode.
There are 2 ways to go out of “In” mode. You may
exit from settings if no button is pressed in 2 minutes, or
by pressing on “A”button.
When “In” is selected by pressing on “B” button in the
menu, “i00” is displayed on screen. It is possible to select any
parameter wished by pressing on DHW(-)(E) and DHW(+)(C)
buttons.
It is possible to select and see value of any parameter by
means of CH(+)(D) and CH(-)(F) buttons.
Any short or open circuit in the sensors are displayed on
screen.
Actual fan speed is always given as rpm/10.
Actual flame current is always given as µAx10
21