7

.3

.

 Operation Functions

7

.3.1

Standby  (OFF Mode):

  The  mode  where  boiler

can  be set to standby  mode. In this  mode, no requests for 
heating  water  and  domestic  water  can  be  made.  To 
activate the OFF mode, it is necessary to keep  button  no. 
1  (position  selector)  pressed  for  3  seconds  continuously. 
When  -OFF-  is  displayed  on screen, mode is activated.

 

7

.3.2

.

  Air  Purge  Mode  (AP  Mode):

 

It  is  the  process

that  the  boiler  automatically  activates  to  discharge  air  in 
the  central  heating  installation  for  160  seconds.  In  this 
mode,  "AP"  is  displayed  on  the  screen.  The  circulation 
pump runs for 15 seconds and then stops every 5 seconds 
in  intervals  of  every  20  seconds.  The  three-way  valve 
motor  also  changes  position  between  a  CH-DHW  in  40 
seconds.  The  situations  where  this  mode  is  activated  is 
listed here below. 

CAUTION: Do not press 'RESET' while 

AP mode is active.

7

.3.3

.

  Winter  mode-Radiator  Heating:

  If  the

boiler  in  the  standby  position  is  set  to  the  winter 
position,  it  will  heat  the  water  in  the  heating  circuit  until 
the  domestic  water  is  needed.  In  the  winter  mode,  both 
the  tap  and  the  radiator  icon  are  displayed  on  the  LCD 
screen.  

When  a  request  for  heating  is  made  for  radiator,  radiator 
icon  flashes  (once/second),  tap  icon  stays  fixed. When a 
request  for  domestic  water  is  made,  tap  icon  flashes 
(once/second),  radiator  icon  stays  fixed.  In  this  mode, 
radiator  heating  circuit's  temperature  can  be  set 
between 

30-

80 

°

C. 

For 

under 

floor 

heating 

applications,  the  temperature  range  can  be  set  between 
30-45 

°

C.

7

.3.4

.

  Summer  Mode:

 

If  the  boiler  in  the  OFF

position  is  set  to  the  summer  position,  the  boiler  will  only 
respond  to  the  domestic  hot  water  demands.  In  summer 
mode,  the  tap  symbol  appears  fixed  on  the  LCD  screen, 
the  radiator  icon  does  not  appear.  When  the  domestic 
hot  water  is  heating  request,  the  tap  symbol  flashes  (1 
time/sec).  In  this  mode,  the  domestic  hot  water 
temperature can be adjusted between 30-

65 °C.

 

7.3.5. Comfort Mode:

 

The standard operating mode of 

the boiler is Comfort mode. By pressing the "Reset" button, 

Eco-Comfort modes can be switched. When Comfort mode 

is  active,  "Comfort"  icon  is  displayed  on  the  LCD  screen. 

Comfort mode is only for radiator heating circuit. It has no 

effect  on  use  of  domestic  water  circuit.  In  this  mode,  the 

boiler  responds  to  fast  heating  demands  by  running  in 

modulation. 

7.3.6. ECO Mode:

 By pressing the "Reset" button, Eco-

Comfort  modes  can  be  switched.  When  Eco  mode  is 

active,  "Eco"  icon  is  displayed  on  the  LCD  screen.  Eco 

mode is only for radiator heating circuit. It has no effect on 

use of domestic water circuit. This mode allows savings on 

fuel by performing on-off operation. 

7

.3.7

Annual

 M

aintanence

 

Reminder

:

 

This  mode  reminds  user

that  “annual  maintanence  time  is  very 
soon”.

 When  this  mode  is  active,  only 

"ASE"  is  displayed  on  screen  and  boiler 
continues  to  meet  heating  requests. 
Electrical  connection  of  boiler  must  be 
always  connected  to  mains,  otherwise 
function will not work properly. When you 
see "ASE" on screen, please check your 
boiler start up date and contact with gas 
safe  engineer  if  annual  maintanence 
period  is  arrived.  If  maintance  of  the 
boiler  is 

done  before  “ASE”  appears  on 

screen,  you  can  skip  it  by  pressing  “R” 

button. 

7

.3.8

.

Anti-Frost  Mode:

During  the  winter 

season,  when  the  installation  water  temperature  falls 
below 

6  °  C, the  anti

-freeze  function  is  activated 

and  the  boiler continues  to  operate  until  the  water 
output  of 

installation  rises  to  15  °  C.  In  order  for 

anti

-freeze  function  to  be  activated,  the  following 

conditions  must  be  checked  and  ensured  by  the 
customer. 

The power supply of the boiler must be switched on.

The gas valve and radiator valves must be open.

Water pressure of system should be at appropriate

level.

The anti-freeze function helps protect your boiler, it

does not protect your installation.

If the boiler will not be operated for a while in places

where there is risk of freezing, then it is necessary

 

to

drain the water or to use an anti-freeze agent

18

Содержание PROTEUS PREMIX 14 HM NG ERP UK

Страница 1: ...INSTALLATION AND MAINTENANCE INSTRUCTIONS PROTEUS PREMIX CONDENSING BOILER PROTEUS PREMIX PPR 14 20 24 28 30 35 HM HCH HST...

Страница 2: ......

Страница 3: ...ULES AND WARNINGS 2 TECHNICAL DATA 3 NOTES ON THE DOCUMENTATION 4 SETUP 5 CONNECTIONS 6 INSTALLATION 7 OPERATION 8 INSPECTION AND MAINTENANCE 9 PART DEFINITIONS MAINTENANCE INSTRUCTIONS 10 INSPECTION...

Страница 4: ...stalled in accordance with national and local requirements gas safety regulations relevant standarts and this manual by gas safe engineer 9 The boiler must be mounted against a closed wall 9 The boile...

Страница 5: ...5 Seasonal Space Heating Energy Efficiency 91 11 91 4 92 2 92 4 92 92 9 Water Heating Energy Efficiency 83 6 83 6 83 6 83 9 82 8 82 8 Sound Power Level db A 49 49 49 49 49 49 Efficiency at Rated Heat...

Страница 6: ...pansion Vessel lt 8 Weight Net kg 28 5 28 5 28 5 30 30 32 Weight Net only for HCH model kg 22 5 22 5 22 5 24 24 26 Dimesions HxWxD mm 678 410 288 Flue Lenghts C13 60 100 Max m 10 10 10 10 10 10 C13 80...

Страница 7: ...centralheating co uk or installersfirst co uk for more information Table 2 Product Definition and Codes PRODUCT NAME PRODUCT CODE GC NUMBER PROTEUS PREMIX 14 HM NG ERP UK 8116941010 47 814 30 PROTEUS...

Страница 8: ...the installation and initial start up of the boiler Instructions are given below Check Operating Instructions Installation and Maintenance Instructions and follow instructions before installation Carr...

Страница 9: ...ervoir 19 Ignition Electrode 20 CH Return Temperature Sensor 21 CH Supply Temperature Sensor 22 Turbine 23 Flue Gas Sensor 3 3 2 HST Model System Boiler Figure 2 HST Boiler 11 12 16 1 15 10 9 8 2 4 3...

Страница 10: ...CH HST Model Automatic Air Vent Expansion Vessel 8 liters Water ingress protection from flue Annual Maintanence Reminder 4 SETUP 4 1 Minimum Clearances 4 2 Dimensions Figure 4 Combi Mounting Clearance...

Страница 11: ...tions 5 1 1 Flue Sizes Flue gas connections between the boiler and the flue terminal must be made using original components specially designed for the condensing boiler to ensure that the boiler opera...

Страница 12: ...minimum distances required from the top and sides of the boiler Dimensions given in mm The installation must comply with the following minimum distances so that servicing and maintenance of the boiler...

Страница 13: ...to the boiler The flue ducts are always wet Under cold or excessive humid weather conditions the water vapor inside the waste gas may condensate while leaving the flue 6 3 Mounting The Boiler Having d...

Страница 14: ...ler CAUTION Disconnect power supply to prevent electrical shock before connecting the electrical supply CAUTION If the supply cord is damaged it must be replaced by the gas safe engineer in order to a...

Страница 15: ...6 8 Installation for HCH Boiler External WRAS appoved filling loop must be added during installation Figure 15 Installation for HCH Boiler Heat Only Type Installation Expansion Vessel 15...

Страница 16: ...rmostat outdoor sensor and timer must be performed certainly by gas safe engineer Room thermostat connection is installed by after removing bridge circuit Outdoor sensor is installed by connecting its...

Страница 17: ...ton When your boiler fails the error code will start flashing on the display There are 2 types of errors lockout EXX and blocking FXX error When a lockout error condition occurs EXX the error must fir...

Страница 18: ...e can be adjusted between 30 65 C 7 3 5 Comfort Mode The standard operating mode of the boiler is Comfort mode By pressing the Reset button Eco Comfort modes can be switched When Comfort mode is activ...

Страница 19: ...on starts to light on the LCD at the first Access the menu When tS is selected by pressing on B RESET button 000 is seen on the screen When B RESET button is pressed again and password entry is displa...

Страница 20: ...P33 OTC curve selection Num 0 0 0 0 0 0 System 1 Emas Hydroblok CCB Pakkens Configuration DHW P37 Water 2 Fugas Hydroblock Num 1 1 1 1 1 1 pressure circuit flow sensor circuit 3 Bitron Hydroblock Heat...

Страница 21: ...is sufficient to press the Reset button once to exit the ASE mode AP Mode During this mode AP and water pressure values will appear on the screen Accessing to Inquiry Mode In Inquriy Menu gives detai...

Страница 22: ...tively When Hi is selected by pressing on B button in the menu H01 is displayed on screen It is possible to select any parameter wished by pressing DHW E and DHW C buttons It is possibble to select an...

Страница 23: ...9 Outdoor temperaure sensor error E15 Drift sensors check failed F40 The water pressure in the CH installation is too high E16 Supply sensor stuck_at test failed F47 Water pressure sensor is not conne...

Страница 24: ...rect YES YES whether e ate trap and check conde a connected at YES NO NO are proper NO YES YES YES e ate trap if it electrode electrode NO float If electrode contact with water replace electrode conne...

Страница 25: ...Replace the gas valve Dismount the gas valve connector Connect the power to the boiler Check whether the resistance at the connector ends coming from the circuit board is in the range of 23 25 V when...

Страница 26: ...ter and return water Check whether resistance values are correct Internal bypass may be not functional Replace the 3 Way Valve Shaft Group Check whether error is gone after Reset YES Pump connection c...

Страница 27: ...board side is latched or look for any loose contact Check whether cable connections are proper and without damage NO Remove igniton electrode and check is there any oxidation present YES Replace the...

Страница 28: ...he gas valve connector Connect the power to the boiler Check whether the resistance at the connector ends coming from the circuit board is in the range of 23 25 V when the boiler is trying to ignite N...

Страница 29: ...oard may be broken Replace main board Replace temperature sensors for CH supply and CH return waters YES NO E16 SUPPLY WATER TEMPERATURE SENSOR FAULT Check whether supply water temperature sensor is m...

Страница 30: ...Main board may be broken Replace main board YES NO E18 TEMPERATURE SENSORS FAULT Temperature change on temperature sensor is too much 30 C Check whether the temperature sensor cables are working prop...

Страница 31: ...nd without damage Replace CH return water temperature cables in case of any problem Check whether there is not any rusting corrosion or deformation inside where it touches to copper pipe or checking w...

Страница 32: ...t doesn t disappear after reset replace the CH supply sensor Replace the main board NO YES E80 FAULT OF TEMPERATURE DIFFERENCE BETWEEN CH TEMPERATURE SENSORS CH return water temperature is higher than...

Страница 33: ...pressure at gas valve inlet must be over 12 mbar Fix installation Press the Reset button Check whether ignition electrode cable electrode and electronic board side is latched or any loose contact YES...

Страница 34: ...ads pressure Fill water into boiler up to 1 5 2 bars NO Access to i 05 parameter in the Inquiry parameter mode determine which temperature the sensor detects and compare it using another measuring dev...

Страница 35: ...e the main board Pertinent intervention is applied according to the last fault in Fault history NO YES F25 Electronic Card Fault Check the error history and turn the boiler off and on again Relevant a...

Страница 36: ...onnector on water pressure sensor when the power of the device is still on and measure the DC voltage Check whether the voltage is in the range of 4 9 5 1 V DC NO YES Replace the main board Replace th...

Страница 37: ...loose contact Check the cables Replace them in case of any problem Replace the outdoor sensor Check whether fault is gone The problem is outdoor sensor Replace the main board YES YES NO NO Check wheth...

Страница 38: ...d measure the DC voltage Check whether the voltage is in the range of 4 9 5 1 V DC YES Replace the main board NO YES Replace the pressure sensor Check whether fault is gone Check whether the pressure...

Страница 39: ...oard F50 STORAGE TANK SENSOR FAULT Ensure that P00 1 for HM model P00 3 4 is used for HST model NO Boiler sensor cables may be not mounted or there may be a loose contact Check the cables YES Fix them...

Страница 40: ...her any problem on PT1000 sensor Resistance Check YES Replace sensor in case of any problem Replace main board NO YES F52 DHW TEMPERATURE SENSOR FAULT NO DHW temperature sensor cables may be not mount...

Страница 41: ...em if there is any damage Check whether any problem on flue gas temperature sensor Resistance Check Replace sensor in case of any problem Replace main board NO YES YES F58 Flue Gas Lock Up at High Tem...

Страница 42: ...isappeared If not Supply return or dhw temperature sensor cables may be not mounted or there may be a loose contact Check the cable Fix them if not mounted replace them if there is any damage Check wh...

Страница 43: ...0 2 24 kW G25 7 75 0 05 6250 1850 2750 3250 9 3 0 2 8 7 0 2 9 5 0 2 8 9 0 2 28 kW G25 8 8 0 05 6500 1900 2750 3300 9 3 0 2 8 7 0 2 9 5 0 2 8 9 0 2 30 kW G25 8 8 0 05 6900 2100 2750 3500 9 3 0 2 8 7 0...

Страница 44: ...ounting Side Panel Unscrew 2 screws affixing the control panel to the side panels NOTE All part changes may be performed without removing the side panels Disassembly of side panels is give for informa...

Страница 45: ...ECTOR NAME FUNCTION X1 Condensate Trap X2 Earth Outdoor Temperature Sensor X3 OpenTherm 3 0 Room Thermostat Program Timer DC Gas valve X4 Fan Driver Interface Flue Sensor Input DHW Instantaneous Senso...

Страница 46: ...ctrode Mount the electrode and grounding cable as shown in the photo NOTE When mounting the electrode you must hear the locking sound as click Dismounting mounting fan cables Mount the cables of fan m...

Страница 47: ...cable Flow sensor Hall Effect sensor in the tap water line shown in the photo Dismounting Mounting gas valve cable Dismounting Mounting surface type NTC and cable There are 2 surface type NTC on CH Su...

Страница 48: ...nting motorized valve Remove the motorized valve by unlatching the clip holding the manifold and the motorized valve Unscrew the screw on the valve motor in order to replace the cable of the motorized...

Страница 49: ...ve Remove firstly the hose at the end of safety valve Remove the connecting screw of lower chassis to the side panel Afterwards unscrew the nut on the manifold using an Allen screwdriver In order to r...

Страница 50: ...as valve and gas pipe using a wrench Placing gas throttle washer Place the orifice washer between 2 seals into the gas valve Mounting dismounting Venturi Remove the clip fastening the gas pipe and ven...

Страница 51: ...pump using a hand tool Unscrew the nut affixing the expansion tank and the flexible hose using a wrench Remove the gripper brackets of expansion tank Mounting dismounting the Main Exchanger group Und...

Страница 52: ...Remove 4 screws of the burner door Follow the order of operations shown as wrench symbol inscribed on the burner door when dismounting and remounting Remove the Duroboard as shown in the photo Remove...

Страница 53: ...terminal block as shown in the photo Mounting dismounting the main board Remove the main board by flexing the notches holding the main board on the control panel Mounting dismounting the mounting par...

Страница 54: ...fold Remove the screws fastening the pump and to bottom consol Mounting dismounting of flow sensor Remove it using a wrench Dismounting of tap water filter Remove the filter on tap DHW inlet pipe usin...

Страница 55: ...arge of exhaust gas from condensate trap s drain to outdoor Primary Relevant Error Codes Troubleshooting and Testing Method Visual inspection and cleaning of any dirt burrs etc inside condensate trap...

Страница 56: ...amage and checking any abnormality of components circuits on the circuit board tarnishing solder cracks splits etc Maintenance Period No special maintenance requirement GAS VALVE Subject Description P...

Страница 57: ...EXCHANGER Subject Description Part Function It is the main component in the central heating circuit enabling heat transfer to water Impact in Case of Faulty Operation 1 Failure to fully meet heating d...

Страница 58: ...meeting tap water demand 2 When all radiator valves are closed it continues its function on water circulation itself internal by pass Impact in Case of Faulty Operation 1 In case of partial of full c...

Страница 59: ...no heat is detected by temperature sensor error 2 No water is heated on tap water demand 3 Freeze protection function fails to work properly 4 Water instead of air comes out of pump air relief cock an...

Страница 60: ...nterclockwise by pressing on the point shown with A using a No 2 screwdriver VENTURI Subject Description Part Function It is the component where gas coming from gas valve and air sucked in from silenc...

Страница 61: ...age 2 Checking whether there is any rusting corrosion or deformation on the immersion probe 2 Resistance check Maintenance Requirement No special maintenance requirement Maintenance Period Testing Def...

Страница 62: ...roper and without damage 2 Checking whether there is any rusting corrosion or deformation on the immersion probe 3 Resistance check Maintenance Requirement No special maintenance requirement Maintenan...

Страница 63: ...ror Codes F37 F40 F47 Troubleshooting and Testing Method Visual Inspection and Testing 1 Checking whether cable connections are proper and without damage 2 Checking whether water inlet of water pressu...

Страница 64: ...ing Method Visual Inspection 1 Checking whether cable connections are proper and without damage 2 Checking whether connectors on the 3 way motor are installed properly 3 Voltage Testing for central he...

Страница 65: ...r discharge of water 2 High pressure error due to no discharge of water 3 Risk of leakage occurrence in plumbing where user continues to fill water after high pressure error Primary Relevant Error Cod...

Страница 66: ...ectrode dimensional measurement controls 3 Ionization flow control 4 Replace electrode and electrode gasket together Maintenance Period Once a year or in any erros due to electrode according to instru...

Страница 67: ...sting Method Measuring the expansion tank gas pressure Maintenance Period Once a year according to instructions below Maintenance Definition Maintenance Method Measuring Expansion Tank Gas Pressure Dr...

Страница 68: ...age 2 Checking whether there is any oxidation etc around the flow sensor cable inlet 3 Voltage Testing 4 Filter cleaning and flow turbine group inspection Note If P00 parameter is 5 the boiler does no...

Страница 69: ...getting its motion from 3 way motorized valve in order to ensure that boiler goes in the summer mode and the winter mode 2 It ensures the internal by pass function when the central heating valves are...

Страница 70: ...o mixing of tap water with the water in the central heating system 4 Where the pressure of main tap water system is very low it may cause low pressure error by emptying water in the central heating sy...

Страница 71: ...e any faults that are found Annually 12 Carry out the combustion analysis Measure the CO content CO content and the CO CO ratio For products with a rear air flue connection The combustion analysis can...

Страница 72: ...After each time maintenance work is carried out 29 Open the service valves carry out the required leak tightness test Annually 30 Fill the product heating installation to the filling pressure specifi...

Страница 73: ......

Страница 74: ......

Страница 75: ......

Страница 76: ...RODUCTION EMAS MAK NA SANAY A Organize Sanayi B lgesi 3 K s m Mustafa Kemal Bulvar No 13 45030 MAN SA T RK YE Phone 90 236 213 00 21 Fax 90 236 213 08 59 E mail emas emas com tr www emas com tr SALES...

Отзывы: