Connection of Horizontal (060/lOOmm) Hermetic Flue Set to the Combi Boiler 

As  your  combi  boiler  is  hermetic  model,  it  takes the  air  used  from  the  external  environment,  and 

discharges the  waste  gases  arising  as  the  result  of combustion  from  the  same flue  group.  The  use 

and  assembly of flue  is  very  important for the  extremely  harmful  waste gases  not  to  be  spread  in 

the environment, thus the warnings should  be  considered while  making the flue connections. 

Horizontal outlets should  be  assembled with  1-2% downwards inclination for 

rain  water etc.  not to  enter the device.  (Figure Sa) 

Horizontal (

Ø

60/100 mm  ) Hermetic Flue Set Consists of the Following Parts; 

1.  Flange gasket 
2.  Flue connection flange 
3.  Flange screws 

4.  Sealing gasket 
5.  90

° 

bend 

6.  Clamp 
7.  Clamp screws 
8.  EPDM  connection gasket 
9.  Flue outlet terminal 
10.  Interior wall  connection flange 
11.  Exterior wall  connection flange(EPDM)

Figure 8 

• Make the  required  flue  selection for the flue  connection to  be  made  to  outer environment from 

the  location  where your combi  boiler  is  assembled.  If the  standard  flue  set  is  insufficient,  select 

the  most  suitable  accessories  from  our  connection  accessories  list  considering  the  warnings 

referred  in  our guide. 

• Fix  the  flue  connection  flange  through  screwing  to  the  holes  on  the  combi  boiler  by  using  the 

flange gasket.  (Figure 9a-9b)

• Place the  2 sealing gaskets -provided by the  hermetic flue set- to  interior pipe slots on  both  ends 

ofthe bend  of 90

°

.

• Apply the  EPDM  connection  gasket  to  the  bend  of 90

° 

as  to  contact  the  limiting  set  inside  the 

gasket. 

• In  order to  group the flue outlet terminal,  apply the  exterior wall  (EPDM)  gasket to  flue terminal 

as  seen  in  Figure  9c.  After  passing the  flue  outlet terminal  through  the  exterior side  of the  wall 

and  from  the  previously  opened  hole,  connect  the  interior  wall  connection  gasket  to  flue 

terminal.  Apply  the  other  end  of  the  EPDM  connection  gasket  of  your  combi  boiler  -which  is 

applied  to  flue  bend  of  90

°

- to  the  flue  outlet  terminal,  and  apply  the  clamp  on  the  EPDM 

connection  gasket and  loosely tighten  it  with  screw  (Figure  9d).  And  then  place  the  bend  of 90

° 

on  the flue  connection flange,  and  fix with tightening screws  (Figure  9e).  Finally,  after tightening 

the  screws which  are  placed  on  EPDM  gasket and  which  are  left  loose,  enable the  flue  and  wall 

tightness by  pushing the  interior wall  connection gasket as to touch the wall. 

Содержание GeliosPlus 11

Страница 1: ...GELIOS PLUS 11 13 16 20 24 28 HM HERMETIC MONOTERMIC COMBI BOILER INSTALLATION AND USER S OPERATING INSTRUCTIONS GeliosPlus ...

Страница 2: ...30 11 10 18 18 19 ...

Страница 3: ... E C A authorized services Your device has 2 years E C A service warranty against all kinds of malfunctions that may arise from material and workmanship provided that it is conformed to instructions and warnings being specified in the assembly and usage guide For the guarantee to be valid you have to have the date of purchase recorded on the warranty certificate provided by the guide and approved by...

Страница 4: ...pliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision The device is consist of sheet metals which have sharp edges that mayg cause injuries Service operation must be done by only authorized people Proper personel protective equipments must be used during service operations...

Страница 5: ... with minimum heat loss has been designed Due to these features of the burner and combustion chamber fuel saving is ensured and alsa minimum noise level is obtained The circulation pump has automatic air relief cock and three cycles and it is suitable far all the installations The device has pump over run feature that prevents thermal accumulation in the installation After ending of central heatin...

Страница 6: ... 76 11 3 32 GELIOS PLUS 11 13 16 20 24 28 HM E C A GELIOS PLUS 11 13 16 20 24 28 kW Hermetic Combi Boiler monothermic model 30 80 If the twin chimney outlet is not available as shown in Figure 14 a twin chimney adapter should be used to install these chimney types 28 HM 90 7 9 5 28 10 5 30 5 3 22 1 12 12 8 2 33 4 33 2 ...

Страница 7: ...OSTAT 6 AIR PRESSURE SWITCH 7 DHW TEMPERATURE SENSOR 8 TURBINE 9 OUTSIDE TEMP Optional 10 PUMP 11 FAN 12 GAS VALVE 13 SUPPLY CABLE 14 3 WAY VALVE 15 POTENTIOMETER DHW TEMP 16 POTENTIOMETER CH TEMP 17 ON OFF RESET SUMMER WINTER MODE 18 FUSE 19 LCD DISPLAY 20 FAILURE LED 21 IGNITION AND IONISATION ELECTRODE ...

Страница 8: ...x 405 HxWxD Figure 2 Figure 2 The parts required for the assembly of the device wall hanger bracket 5 gaskets for water and gas connections 3 dowels and lock screws has been placed on the top styrofoam Assembly bracket Central heating water connection pipes 3 4 2units Domestic hot water connection pipes 1 2 2units Gas inlet pipe 3 4 1 unit Nipples l 2 2 units 3 4 3 units 6 units 3 4 gasket and 4 u...

Страница 9: ...ure of the device doesn t exceed 85 C at maximum heating power special protective measure against flammable construction materials and elements is not required The following limitations have been imposed by TSE and authorized gas institutions for the locations where the hermetic device will be assembled Assembly of devices should be performed at Stairwells of the buildings Corridors of the buildin...

Страница 10: ...Min distancetothe roof Human area Vehicle area ...

Страница 11: ...nce grille from the outside 30 of the building C Below rain channel 30 I Distance from the inner corner of the 100 buildina D Under the balcony 30 L From the ground or from the fioor 180 E Next to a window 40 M Vertical distance of two fiue outlets 250 F Next to an air grill 60 N Horizontal distance of two fiue outlets 100 Figure 4b Figure 4a 9 ...

Страница 12: ...gas outlets of these devices should be 30 cm below the bottom edge of the window Figure 5c C type devices below the ground level at basements can only be installed if the combustion air and was gas pipe lines of each device are opening to their own channels The cross section areas of the channels should be at least 0 75 m2 and the small edge size of the channel should be at least 0 5 m There shoul...

Страница 13: ...n pipe In respect of preventing condensation in the pipes the part of hermetic flue group remaining at the roof space should be isolated d Figure 5 Issues to be Considered in Flue Connections e After determining the location where the combi boiler will be assembled The locations of lock screws of wall hanger bracket and assembly bracket are marked by using the assembly template on the last page of...

Страница 14: ... ø 60 100 mm up to max 4 meters 2 Vertical flue connection ø 60 100 mm up to max 4 meters 3 Twin flue connection ø 80 80 mm up to max 8 meters for 28 kW 1 5 meters 2 6 meters 3 12 meters for 28 kW 5m for 28 kW 4m for 28 kW 4m 5 12 ...

Страница 15: ...select the most suitable accessories from our connection accessories list considering the warnings referred in our guide Fix the flue connection flange through screwing to the holes on the combi boiler by using the flange gasket Figure 9a 9b Place the 2 sealing gaskets provided by the hermetic flue set to interior pipe slots on both ends ofthe bend of 90 Apply the EPDM connection gasket to the ben...

Страница 16: ...ermetic flue accessories should be ordered from an authorized E C A vendor as per requirement and other hermetic flue accessories should not be used Ø60 lOOmm Hermetic Flue Set Accessories Figure 10 a Extension pipe 500 mm EPDM gasket clamp and clamp screws Extension pipe 1000 mm EPDM gasket clamp and clamp screws Figure 10a b Bend of 90 EPDM gasket clamp and clamp screws Figure 10b a b Figure 10 ...

Страница 17: ...Restrict or Fan 43 GELIOS PLUS 24 20 kW 39 GELIOS PLUS 16 13 11 kW 43 GELIOS PLUS 28 kW 4 5 5 47 47 4 47 47 15 ...

Страница 18: ...16 3 6 7 1 2 4 5 ...

Страница 19: ...43 GELIOS PLUS 24 20 kW 17 39 GELIOS PLUS 16 13 11 kW 5 4 3 4 5 5 4 3 4 5 ...

Страница 20: ...18 L3 L1 L2 L2 L1 Lmaks 4m Ø60 100 for 28 kW 6m 4m 3m 5m for 28 kW 5m for 28 kW 4m 43 GELIOS PLUS 28 kW 6 5 4 4 5 5 6 4 5 47 47 47 47 47 ...

Страница 21: ...43 GELIOS PLUS 24 kW GELIOS PLUS 20 kW GELIOS PLUS 16 kW GELIOS PLUS 13 kW GELIOS PLUS 11 kW 8 8 8 8 8 43 12 GELIOS PLUS 28 kW 19 ...

Страница 22: ...20 Figure 18a Option 1 Figure 18b Option 2 67 66 ...

Страница 23: ...21 ...

Страница 24: ...the combi boiler is made All the radiator valves are opened The valves of central heating outlet return lines of the combi boiler should be open Check it After this operation start the filling operation by slowly opening the filling valve ...

Страница 25: ...23 ...

Страница 26: ...on selection button to the right to the bar symbol In this position water pressure will be shown on screen 24 If the button is left at bar position boiler will run in summer mode so central heating system will not get hot water 30 ...

Страница 27: ...Flame Signal 25 30 CH Pressure Value ...

Страница 28: ...26 ...

Страница 29: ...27 12 3 1 4 28HM 11 9 1 25 ...

Страница 30: ...28 For 28 kW there are 13 injectors on the boiler ...

Страница 31: ...Error Maltunction Codes 29 9 ...

Страница 32: ...30 F1 Overtemperature locking 9 ...

Страница 33: ...950mm 1 740mm 8 3 3 31 ...

Страница 34: ...320mm for 28 kW 5m 32 ...

Страница 35: ...0 1 2 3 4 5 6 0 500 1000 1500 2000 2500 3000 Head mH20 water flow rate l h Flow Head Curve III II I 2 33 for 28 kW for 28 kW ...

Страница 36: ...34 7006907068 1 0 ...

Отзывы: