Product Manual WS74
__________________________________________________________________________________
Copyright
DZG Metering GmbH, Heidelberger Str. 32, D-16515 Oranienburg
Copies only are allowed authorized by DZG
2/22/2019
Page 35 / 37
14.5
Status word
Only L1 status supported.
Bit pos.
Meaning
Set to ‚1‘, if …
Set to ‚0‘, if …
0
Status word identification (LSB)
-
Always to ‘0’
1
Status word identification
-
Always to ‘0’
2
Status word identification
Always to ‘1’
-
3
Status word identification
-
Always to ‘0’
4
Status word identification
-
Always to ‘0’
5
Status word identification
-
Always to ‘0’
6
Status word identification
-
Always to ‘0’
7
Status word identification (MSB) -
Always to ‘0’
8
Idleness/starting in the active
power unit of the measuring
element
‘1’
starting.
Set to ‘1’ if the active
power summation current
over all conductors is
greater than or equal to I
st
as specified in
DIN EN 50470-1 (
starting current).
The active power
summation current is the
signed sum of the active
power part of all the
conductor currents.
Set to ‘0’ if the active
power summation current
over all conductors is less
than the starting current.
9
Manipulation magnetic interface
The status bit is required only if
the optional manipulation
detection is present.
It shall be set to ‘0’ if the meter
is impossible to be magnetically
interfered with within the limits
defined in the Reliability
Specification (see FNN
Leitfaden Zuverlässigkeit)
‘1’
interference
detected
Is set to ‘1’ if the meter
detects a DC magnetic
field in accordance with
(
FBZ_0320)
.
Measurement setup see
Paragraph (124).
Reset to ‘0’ at voltage
recovery or 24 h (
10 %)
after dropping below a
certain limit.
10
Manipulation
Terminal cover (3.HZ) or
Locking pin (eHZ)
‘1’
interference
detected
Is set to ‘1’ when the
terminal cover is lifted, or
the locking pin loosened.
Reset to ‘0’ at voltage
recovery or 24 h (
10 %)
after the condition
‘Manipulation of terminal
cover or locking pin
detected’ is ended.
11
Energy direction, sum
This status bit is always present
and therefore independent of the
measurement element variant
(see item ‘Metering type’ in
Table 14).
For idleness of the active power
unit the condition ‘0’ shall be
assumed.
‘1’
-A
‘0’
+A
12
Energy direction L1
The specification for the status
bit energy direction sum apply.
‘1’
-A
‘0’
+A
13
Energy direction L2
‘1’
-A
‘0’
+A