Registers
14.1
Instantaneous data
This registers can be read out via the optical interface if the meter is ordered with this option.
The registers are not shown on the display.
Access Level
R: read only
R/W: read/write
M: write only in manufacturer mode
No.
Name
OBIS
(Hex notation)
Length
Format
Unit
Acces
s
level
1.
Phase L1 voltage
01-00:20.07.00*FF
4
U32 Hex,Big Endian
0.01V/bit
R
2.
Phase L1 current
01-00:1F.07.00*FF
4
U32 hex,Big Endian
0.001A/bit
R
3.
Phase L1 Active power
01-00:24.07.00*FF
4
S32 hex,Big Endian
0.01W/bit
R
4.
Phase L1 power factor
01-00:21.07.00*FF
2
U16 hex,Big Endian
0.001 PF/bit
R
5.
Frequency
01-00:0E.07.00*FF
2
U16 hex,Big Endian
0.1Hz/bit
R
6.
Phase angle I-L1 to U-L1
01-00:51.07.04*FF
2
U16 hex,Big Endian
0.1 °/bit
R
Table 9 Instantaneous data