PowerDepot H5 series User Manual
21
(7) Generally the DIP switch of the slave module no need to be changed,keep it 0000;But for
ICC,it needs to be changed to 0001 .
(8)When the PowerDepot H5 are used in parallel,you need set the master PowerDepot DIP
switch mode as above,and set all the modules DIP switch in slaves PowerDepot to
0000(include the host module in slave PowerDepot),it’s 0001 for ICC,this is very important.
Note: For more information of matching inverter brands, please subject to the latest document
<The list of compatibility between Dyness ESS and Inverters >.
Caution
1. The DIP switch Mode 4 and Mode 6 is only for ICC(a special commnunication device for some
no-
communication inverter), it’s a specia firmware in P
owerDepot H5,different from general
firmware,so if customers want to use that,please contact dyness to confirm.
2. Generally factory default DIP switch status of the host module in PowerDepot H5 is Mode 1.
When they are used in parallel, all the slave PowerDepot H5 systems need to be opened the
cover and change the DIP switch of the host module to Mode 5 (i.e. ADD: 0000),the master
PowerDepot no need change.
Proceed as follows:
Factory default is in“OFF”state(500K)
Should be dialed to “ON”(250K) for ICC