Powerbox F series User Manual
8
Item Name
Definition
When the system is used in parallel:
This CAN/RS485 communication socket is connected to the COM
IN interface of the next Powerbox through communication cable.
(Factory default CAN communication mode)
5
LED1
Module 1 status indicator light
6
LED2
Module 2 status indicator light
7
LED3
Module 3 status indicator light
8
LED4
Module 4 status indicator light
9
Ground
connection point
Shell ground connection
10
Reset switch
Press the switch and the battery system turn on.
When the battery is in the nonuse state such as storage,
transportation etc., it needs to be turn off by pressing the Reset
switch button, and the battery system will automatically sleep
after the device without external load and power for 72 hours.
11
DC circuit
breaker
Protective circuit
Table 2-4 LED status indicators (Take Powerbox F 10.0 as an example)
State
Protect/
Alarm/
Normal
Led1
Led2
Led3
Led4
Directions
Shut down
off
off
off
off
All off
Stand-by
Normal
●
●
●
●
Always on
Alarm
●
●
●
●
Always on, Corresponding module
capacity 5%<
SOC≤10%
Protection
●
●
●
●
Flashing, (Corresponding module
capacity,
0%≤SOC≤5%/Low voltage
alarm / Over-discharge protection /
Over-charge protection / Over-current
alarm or protection / Hardware failure /
Temperature abnormality, etc.)
Charging/disc
harging
Normal
●
●
●
●
Always on
Alarm
●
●
●
●
Always on, Corresponding module
capacity 5%<
SOC≤10%, Over
-charged
alarm.
Protection
●
●
●
●
flashing, (Corresponding module
capacity
, 0% ≤SOC≤5% /
Low voltage
alarm / Over-discharge protection /
Over-charge protection / Over-current
alarm or protection / Hardware failure /
Temperature abnormality, etc.)