2.3  Electrical Installation

Electrical connections are made to the sensor module through a standard 1/2 inch NPT liquid tight flexible conduit. The nipple 
length may be changed to extend the outlet box if desired. Interconnection cable recommendations are as follows: stranded 
copper, 22 through 16 gage, braided or foil with drain wire shielding 0.05 

µ

F maximum total mutual or direct capacitance, 

outer sheath insulated. Shrink tubing may be placed over any wires without insulation. For lengths over 100 feet, use 18 gage 
or larger, to  a maximum of *1000 feet. If shielded twisted pair wire is used, do not cross channels. Keep each pair of 
complementary channel outputs together in a single twisted pair (e.g., A and A complement). 

U

*NOTE

U

: Provides CE compliance in applications where cable length is less than 30 meters. 

U

CAUTION!

Reversing power and common will not damage the unit. However, applying power to  
any of the sensor outputs may cause damage.

Table 1. Signal Coding Table

Signal

Connector Pin

Pigtail Cable

MS 3102E18-IT#

Common
B
A
Z *
No Connection
Vcc (5-15 VDC)
/B
/A
/Z *
Shield

1
2
3
4
5
6
7
8
9

10

Black
Green
Blue
Violet
-----
Red
Yellow
Gray
Orange
Braid

F

B
A
C
E
D

I

H

J

G

*  Applies only to units with index pulse capability.
#  Pinouts are for the sensors with the MS 3102E18IT connector

NOTE

The shield in the sensor module is isolated from the frame of the encoder for maximum  
noise immunity. The shield wire or pin should be connected to the shield of the cable and  
that of the drive or other receiving device.

10                                                                    

©

 

DYNAPAR                                                              +1.800.873.8731 

Grounding: 

For applications with high ground potential differences, DO NOT ground the encoder through both 

machine and controls end. Connect the shield at the controls end only. 

NOTE: If the shield is connected at 

both ends,

 

grounding problems that degrade system performance can result.

 

CE Grounding Measures 

– For best EMC immunity the cable screen must be grounded on both encoder and 

controls end. For cable lengths longer than 30m or outdoor applications, additional measures must be 
implemented to comply with CE requirements. Connection of the encoder to DC power supply network is 
prohibited if CE compliance is required. CE-compliant products are tested to EN61326-1 EMC.

In all cases, system CE compliance is ultimately the responsibility of the manufacturer integrating the encoder.

Содержание NorthStar SLIM Tach SL56

Страница 1: ...APAR 1 800 873 8731 791 1007 00 Rev H Website www dynapar com brand Customer Service Tel 1 800 873 8731 Fax 1 847 662 4150 custserv dynapar com Technical Support Tel 1 800 234 8731 Fax 1 847 782 5277...

Страница 2: ...2 DYNAPAR 1 800 873 8731...

Страница 3: ...ector 11 2 5 Returning NorthStar brand Equipment to Dynapar 11 Methods and apparatus disclosed and described herein have been developed solely on company funds of Dynapar No government or other contra...

Страница 4: ...from all electrical power sources and 3 all accessory devices associates with the work area have been de energized If high potential insulation test is required follow procedures and precautions outli...

Страница 5: ...s the passing magnetic pulses actuate the magnetoresistive sensor The resulting electronic signals are processed into square wave signals by the internal electronics 5 DYNAPAR 1 800 873 8731 ULatching...

Страница 6: ...airs Input Voltage 5 0 to 15 0 VDC Mechanical Specifications Maximum Operational Speed 5 000 RPM Nominal Air Gap 0 019 0 008 inch Shaft Axial End Play Up to 0 045 inch maximum Enclosure Configuration...

Страница 7: ...ce company Please advise us of such filing In case of parts shortages advise us immediately Dynapar cannot be responsible for any missing parts unless notified within 60 days of shipment 2 1 Motor Fac...

Страница 8: ...shaft until the edge of the pulse wheel is flush with the machined recess in the encoder frame See Figure 4 We recommend you use a straight edge for this purpose For best results align the two surfac...

Страница 9: ...me Insert and tighten four Phillips head screws This completes the mechanical mounting of the unit UNOTE Be sure the letter Z and This Side Out are visible on the face of the pulse wheel after install...

Страница 10: ...o Connection Vcc 5 15 VDC B A Z Shield 1 2 3 4 5 6 7 8 9 10 Black Green Blue Violet Red Yellow Gray Orange Braid F B A C E D I H J G Applies only to units with index pulse capability Pinouts are for t...

Страница 11: ...body and Sensor Module can be improved by smearing a sealant silicone grease etc on the neoprene seal of the connector 5 Mate connector into place on sensor mount and snap the two latches into place...

Страница 12: ...31 Fax 1 847 662 4150 custserv dynapar com Technical Support Tel 1 800 234 8731 Fax 1 847 782 5277 northstar techsupport dynapar com Website www dynapar com European Sales Representative Hengstler Gmb...

Отзывы: