A. Line: This LED indicates whether the supply voltage to the Metering Unit falls within the
specified limit of +10%, -15% of nominal. Significant changes from these values will
cause this LED to turn off, and trip the relay.
B. Hall P.S.: This LED indicates whether the Hall plate voltage supply output falls with the
specified operating limit. A failed Hall plate power supply or a line voltage out of
specification will extinguish this LED and trip the relay.
C. Channel LEDs: Each channel LED indicates the status of the corresponding channel to
aid in quick troubleshooting. An extinguished channel LED can be caused by the
following:
A.)
A blown channel fuse;
B.)
a bad connection between the cable and the Metering Unit or cable and
Measuring Head;
C.)
a bad Hall device in the head;
D.)
an open /or shorted coil in the head;
E.)
a primary current that exceeds the dynamic measuring range of the Metering
Unit;
F.)
the primary current is too low to activate all channels properly;
G.)
a strong external magnetic field causing a channel reversal.
Notes on items f and g above:
1.) Under certain conditions, external magnetic fields can reverse one or more channels in
the head. The accuracy indicators will show an error in those channels until the bus
current level rises high enough to effectively turn on all channels (2-3Vdc is the
minimum reliable channel voltage). This condition can cause false alarms. For more
information on this, please refer to technical bulletin TEC9908, “Resolving External
Magnetic Field Errors”.
2.) In some installations, when the channel voltages are balanced, the channel LEDs will
remain on, even though the bus is turned down to zero. In this case, the accuracy
diagnostics circuit is in an unstable condition and alarm faults, as indicated by the
channel LEDs, should be ignored. Note that, in general, the Metering Unit’s 0.1%
accuracy is only guaranteed when the primary bus current is above 5% of the full scale
rating of the unit.
A relay contact output is available to connect to a remote warning system. The relay is
closed under normal operating conditions and opens when a fault condition occurs. The
output connections are available via a connector located on the left side of the Metering
Unit. The terminals are designated on the appropriate interconnection diagram. The
terminals are used as follows:
Contact Terminals
Condition
TS2-17,18
TS2-18,19
Open
Closed
Fault condition, zero bus current*, or
Metering Unit turned off
Closed
Open
Normal operation
•
see notes above on zero bus current condition.