Installation, Operation and Service Manual
LKP Series
© 2016 DynAmp, LLC
Page 8
041749 K
TABLE 4.1
LKP SERIES 16 CHANNEL SPECIFICATIONS, CONTINUED
OUTPUTS
Current output:
1 A/5 kA, ±0.1% full scale
Voltage output, ALL
1mV per kA of bus current, ±0.1% full scale
PHYSICAL
Overall Dimensions, in. (mm):
LKP Metering Unit (all)
66 (1676)
H
x 48 (1220)
W
x 16 (406)
D
LKP-180 Measuring Head (Version 1)
78.3 (1989)
H
x 111.1 (2823)
W
x 25.2 (640)
D
LKP-180 Measuring Head (Version 2)
102.2 (2597)
H
x 101.3 (2572)
W
x 25.2 (640)
D
LKP-300 Measuring Head (Version 1)
97.4 (2473)
H
x 142.8 (3627)
W
x 25.2 (640)
D
LKP-300 Measuring Head (Version 2)
130.4 (3310)
H
x 129.1 (3280)
W
x 25.2 (640)
D
LKP-400 Measuring Head (Version 1)
118 (2999)
H
x 169.7 (4310)
W
x 31.9 (810)
D
LKP-400 Measuring Head (Version 2)
156.2 (3967)
H
x 153.87 (3908)
W
x 31.9 (810)
D
Max. Aperture Dimensions in. (mm):
LKP-180 Measuring Head (Version 1)
59.4 (1508)
H
x 93.2 (2368)
W
LKP-180 Measuring Head (Version 2)
83.8 (2116)
H
x 83.3 (2116)
W
LKP-300 Measuring Head (Version 1)
76.4 (1939)
H
x 123 (3123)
W
LKP-300 Measuring Head (Version 2)
108.7 (2760)
H
x 108.7 (2760)
W
LKP-400 Measuring Head (Version 1)
92.9 (2360)
H
x 146.8 (3730)
W
LKP-400 Measuring Head (Version 2)
131 (3328)
H
x 131 (3328)
W
NOTE
The Measuring Head window insulation rating is directly proportional to the clearance of the
head to the bus. For instance, a bus in direct contact with the window insulation of the head will
have an insulation rating of 6kV. A clearance of 1" increases the window insulation rating to 12
kV. Thus, the greater the distance through the air between the bus and the head, the greater
the insulation rating will be.
TABLE 4.2
TYPICAL ERROR AT ZERO BUS CURRENT*
Models
Max. Core Set
LKP-180
±27 amperes
LKP-300
±45 amperes
LKP-400
±60 amperes
* Excluding effects of external buses. See section concerning the magnetic effects of external
buses.