3.1 CONFIGURATION MENU

Upon applying power, the unit will display the Dwyer

®

 logo on the screen. If the unit 

is not yet configured, it will go through the initialization sequence and begin the setup 

wizard.  If  the  unit  is  configured,  it  will  show  the  home  screen. After  the  unit  goes 

through the initialization sequence, the screen will display the home screen, which is 

the view that will be continuously displayed. To access the Configuration menu from 

the home screen, press the Settings (gear icon) button in the top right corner of the 

screen.

3.2 INITIAL SETUP WIZARD

The RSMC will load the setup wizard, which will guide the user through the initial 

setup.  The  screen  will  appear  in  the  order  below  and  can  be  navigated  using  the 

touchscreen interface. 

•  Language selection

•  USB Configuration or Local Configuration
  ° If USB is selected, the setup wizard moves to a screen instructing how to copy 

      parameters with the USB stick. Then the setup wizard moves to the Room 

      Settings to allow the Room Name to be changed; followed by the Save/

      confirmation screen. A USB-C to USB-A drive must be used to copy parameters 

      from one RSMC to another. 
  ° If Local is selected, it will move on to the next steps below.

•  Display mode

• Communications

• Inputs

• Outputs 

• Alarm

•  Room settings

•  Display settings

•  Save/confirmation screen

In  the  Configuration  menu,  one  of  three  modes  to  display  the  parameters  can  be 

selected.

1.  1 Room: Monitoring of 4 parameters: 1 binary signal (1 door contact), 1 built-in \ 

    differential pressure, and 2 analog or BACnet inputs to be select by the user.

2.  2 Rooms: Monitoring 4 parameters: 1 built-in differential pressure, 2 analog or 

    BACnet inputs to be select by the user, and 2 binary contacts.

3.  3 Rooms: Monitoring 6 parameters: 1 built-in differential pressure, 2 analog or 

    BACnet inputs to be select by the user; and 3 binary contacts (wired in series).

Examples of 1 room, 2 room, and 3 room setups are shown below.

3.2 LANGUAGE SELECTION

The RSMC supports English and Spanish languages, additional languages will 

become  available  via  firmware  updates. To  select  the  desired  language,  press  the 

Settings (gear) icon on the home screen, then select “Language.” 

3.3 USB CONFIGURATION

The RSMC can be setup with a USB drive. A USB-C to USB-A drive must be used 

to copy parameters from one RSMC to another. The Duplicate Cloning menu 

can be accessed by clicking on the Settings(gear) icon on the home screen, then 

Maintenance, then Duplicate Cloning. 

Duplicate/Cloning permits copying the RSMC configuration to and from a USB thumb 

drive - the purpose of this is to replicate the configuration on other devices or units 

that may be replaced in the field. Please refer to section 6.3 for Duplicate Cloning 

instructions.

3.4 DISPLAY MODE

The home display is configurable and can be adjusted to the end users needs. To 

access the Display Mode, click on the settings icon on the home screen, then select 

Display Mode. The user can select 1 to 3 rooms and 1 to 3 sensors. 

3.5 NETWORK

The RSMC is capable of Modbus

®

 RS-485 and BACnet communications. To access 

the network settings, click on the settings icon on the home screen, select configurator, 

then select Network. Set Modbus

®

 or BACnet MS/TP network information in the 

Network screen. 

Содержание StabiliSENSE RSMC Series

Страница 1: ...ironment such as a clean room or isolation room and an area outside the room Maintaining a constant differential pressure between the two spaces is critical in ensuring the room is protected by ingress for the outer room or vice versa The RSMC can be programmed to monitor either positive or negative room static pressure in 1 to 3 locations In total it can monitor up to 4 parameters built in differ...

Страница 2: ...touchscreen operation when changes in room conditions are needed when additional information is desired or if alarms need to be acknowledged A few of the key elements of the screen are described and shown below The RSMC provides visual representation where each of the parameters are either in normal green within the caution stage yellow in the alarm state red and in cleaning mode blue The caution ...

Страница 3: ... and 2 analog or BACnet inputs to be select by the user 2 2 Rooms Monitoring 4 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 2 binary contacts 3 3 Rooms Monitoring 6 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 3 binary contacts wired in series Examples of 1 room 2 room and 3 room setups are ...

Страница 4: ...ter For example 0 VDC corresponds to the minimum range of the sensor and 5 VDC corresponds to the maximum range of the sensor In the Measurement box the user can define the type of measurement temperature humidity etc and the desired engineering units to be displayed If ACH Air Changes per Hour is selected duct dimensions need to be entered when the input type is selected as volumetric flow When u...

Страница 5: ...try and personnel access Return to Normal delay is the opposite when a parameter value goes out of alarm and now falls within normal range the audible visual and output alarm conditions will persist for this period of time or until the alarm condition is cleared Alarm Deadband is a value that is added or subtracted to a limit when determining if a parameter has returned to a normal state For examp...

Страница 6: ...the sensor assigned to the display position to the right next to Select Sensor If the BACnet option is selected the user has to input the BACnet address and sensor type of the remote sensor After completing the room settings the user can select each parameter from each room in order to use it at the alarm configuration or output configuration Each parameter is named with the room name and the sele...

Страница 7: ... the output value and the user can also change the state 6 0 MAINTENANCE The Maintenance menu provides several functions that help ensure the RSMC is configured and operating accurately with proper parameters To access the Maintenance menu from the home screen press the Settings icon in the top right corner and select the Maintenance button Within the maintenance menu the following maintenance fun...

Страница 8: ...rom the home screen press the Settings icon in the top right corner From the Maintenance menu select Reset A factory reset may help establish a baseline of original functionality from which to build the specific configuration for a given application New configurations can then be added by either touchscreen entry Copy from USB or over the BACnet network Selecting NO will cause the RSMC unit to rem...

Отзывы: