1 room
2 rooms
3 rooms
3.1 CONFIGURATION MENU
Upon applying power, the unit will display the Dwyer
®
logo on the screen. If the unit
is not yet configured, it will go through the initialization sequence and begin the setup
wizard. If the unit is configured, it will show the home screen. After the unit goes
through the initialization sequence, the screen will display the home screen, which is
the view that will be continuously displayed. To access the Configuration menu from
the home screen, press the Settings (gear icon) button in the top right corner of the
screen.
3.2 INITIAL SETUP WIZARD
The RSMC will load the setup wizard, which will guide the user through the initial
setup. The screen will appear in the order below and can be navigated using the
touchscreen interface.
• Language selection
• USB Configuration or Local Configuration
° If USB is selected, the setup wizard moves to a screen instructing how to copy
parameters with the USB stick. Then the setup wizard moves to the Room
Settings to allow the Room Name to be changed; followed by the Save/
confirmation screen. A USB-C to USB-A drive must be used to copy parameters
from one RSMC to another.
° If Local is selected, it will move on to the next steps below.
• Display mode
• Communications
• Inputs
• Outputs
• Alarm
• Room settings
• Display settings
• Save/confirmation screen
In the Configuration menu, one of three modes to display the parameters can be
selected.
1. 1 Room: Monitoring of 4 parameters: 1 binary signal (1 door contact), 1 built-in \
differential pressure, and 2 analog or BACnet inputs to be select by the user.
2. 2 Rooms: Monitoring 4 parameters: 1 built-in differential pressure, 2 analog or
BACnet inputs to be select by the user, and 2 binary contacts.
3. 3 Rooms: Monitoring 6 parameters: 1 built-in differential pressure, 2 analog or
BACnet inputs to be select by the user; and 3 binary contacts (wired in series).
Examples of 1 room, 2 room, and 3 room setups are shown below.
3.2 LANGUAGE SELECTION
The RSMC supports English and Spanish languages, additional languages will
become available via firmware updates. To select the desired language, press the
Settings (gear) icon on the home screen, then select “Language.”
3.3 USB CONFIGURATION
The RSMC can be setup with a USB drive. A USB-C to USB-A drive must be used
to copy parameters from one RSMC to another. The Duplicate Cloning menu
can be accessed by clicking on the Settings(gear) icon on the home screen, then
Maintenance, then Duplicate Cloning.
Duplicate/Cloning permits copying the RSMC configuration to and from a USB thumb
drive - the purpose of this is to replicate the configuration on other devices or units
that may be replaced in the field. Please refer to section 6.3 for Duplicate Cloning
instructions.
3.4 DISPLAY MODE
The home display is configurable and can be adjusted to the end users needs. To
access the Display Mode, click on the settings icon on the home screen, then select
Display Mode. The user can select 1 to 3 rooms and 1 to 3 sensors.
3.5 NETWORK
The RSMC is capable of Modbus
®
RS-485 and BACnet communications. To access
the network settings, click on the settings icon on the home screen, select configurator,
then select Network. Set Modbus
®
or BACnet MS/TP network information in the
Network screen.