RMO25W Getting Started
6.6 Viewing the Test Results
Once a test is finished, RMO25W automatically changes to the
Res
menu to
display the test results.
Note:
In case of PC and RMOWin-W software use during the test, all
performed measurements will be registered with one decimal figure
more than in
Res
menu.
If the defined test current could not be reached, this could be due to a
too high contact resistance of the test object and/or of the current cables.
The test current value displayed here is the maximum test current
reached.
6.7 Viewing Results of Previous Tests
RMO25W stores up to 100 test results. They can be viewed using the
Mem
menu at memory positions 0 ... 99.
Go to
Mem
menu using
LEFT,
and then
UP
button.
Selecting a memory position on the
Mem
menu displays:
• the current fed into the test object,
• the memory position of these results,
• the test object’s measured resistance R1 (left channel) or R2 (right channel),
• the date or the time,
of this particular test.
To view the measured resistance R2 rather than the resistance R1, position the
cursor on the first letter of the
Mem
menu (here M), and use the
LEFT
button to
toggle between resistance R1 and R2.
To view the creation date of the test rather than the time, position the cursor on
the latest number of the memory position (here
0
), and use the
RIGHT
button to
toggle between date and time.
Figure 6-8:
The
Res
menu
showing the test
results
Test current
Memory
position
that holds
the results
Measured resistances of the test objects
Figure 6-9:
The
Mem
menu
showing the
previously saved
test results of
memory position
40