background image

OPUS 

SERIES

INSTALLATION, OPERATION, MAINTENANCE 

AND REPAIR MANUAL

7

9. OPERATING MODES AND 

    SELECTION CRITERIA

OPUS circulation pumps, with their ECM technology, 

provide operating modes that act in accordance with 

the variable flow requirement.

As the working point of the pump shifts to the left, that is, 

the flow rate decreases, the following occurs:

► 

In manual mode, the head is increased.

In constant pressure operation mode, the speed 

decreases and the head remains constant.

► 

In variable pressure operating mode, the rotation 

speed decreases linearly so that the head drops to half 

of the set head value.

9.1 Manual Operating Mode

Figure 9.2: Manual Operation Mode Display
In this operating mode, the pump operates at the set 

rotation speed. The desired speed can be selected.

9.2 Constant Pressure Operating Mode

Figure 9.3: 

Constant Pressure Operating Mode Display

In this operating mode, the pump operates by changing 
the rotation speed so that the set pump head (Hsetting) 
remains constant.
The Hsetting value of the pumps selected in accordance 
with the operating point is determined as follows:

► 

The H value at the operating point is marked on the 

constant pressure operating mode graph.

If the marked point is on any operating mode curve 

belonging to a multiple of 0.5, the H value of that 
operating mode curve is accepted as the Hsetting value.

If the marked point is not on any operating mode 

curve belonging to 0.5 multiples, the nearest operating 
mode curve is passed and the H value of that curve is 
accepted as the Hsetting value.

The operating mode curves are plotted on the graph 
at 1 meter intervals. The setting can be selected on the 
screen in 0.5 meter increments.

9.3 Variable Pressure Operating Mode

Figure 9.5: 

Variable Pressure Operating Mode Display

İzolasyon Vanası

İzolasyon Vanası

Şekil 4.2.4 B

H

setting

 

H

setting

/2 

Pump Head

 

Flow Q (m3/h) 

 

 

Pu

mp

 H

ea

H

setting

 

Flow Q (m3/h) 

OPUS Operating Modes 

Manual 

Constant pressure 

Pu

m

p Head

 

Flow Q (m3/h) 

Variable p ressure  and  constant 

pressure  operating m odes 

provide  energy s avings b y 

following curves according to the 

variable load requirement of the 

system. 

 

Pump Hea

Flow Q (m3/h) 

Содержание OPUS 0-12 280 V

Страница 1: ...SERIES INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL OPUS...

Страница 2: ...2 OPUS SERIES INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL www duyarpompa com...

Страница 3: ...ng and Air Drain 8 6 4 Cable Fuse Selection and Electrical Installation 8 7 DISPLAY AND SETTINGS 10 7 1 Operating Modes 11 7 1 1 Manual Operating Mode 11 7 1 2 Constant Pressure Operating Mode 11 7 1...

Страница 4: ...should be as in Table 3 2 3 4 Operating Conditions OPUS circulation pumps have been developed for the circulation and pressurization of the water circulating in the heating and air conditioning system...

Страница 5: ...code Tracking Number 7 Input Voltage Voltage 8 Minimum Power 9 Minimum Current 10 Temperature Class 11 Input Frequency 12 Maximum Power 13 Maximum Current 14 Serial number 15 QR Code 16 Year of produc...

Страница 6: ...installation pressure should be between the values in Table 5 1 and Table 5 3 The pump must be operated for a while to drain the air from the installation 6 4 Cable Fuse Selection and Electrical Inst...

Страница 7: ...ichever type of pump is to be used it must be selected according to the nominal current and voltage of that pump and a B type relay which can open at DC current and high frequency Grounding current sh...

Страница 8: ...conds to set the target speed in night work When the P7 option is reached with the button when the target speed is reached with the keys by pressing the P button again the speed record is made by keep...

Страница 9: ...ng remains constant The Hsetting value of the pumps selected in accordance with the operating point is determined as follows The H value at the operating point is marked on the constant pressure opera...

Страница 10: ...selected on the screen in 0 5 meter increments 9 4 Operating Mode Selection Criteria The operating mode is selected by considering the criteria in the table below Table 9 1 Operating Mode Selection Cr...

Страница 11: ...INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL 9 10 TERMINAL CONNECTION DETAIL 10 1 Terminal Connection Detail Table 230 VAC DIN1 Communications BSM RS485 Relay Link DIN2 communication devices...

Страница 12: ...will start stop from digital 1 and from the buttons on it in Manual mode P17 DN2 selection 0 Dysfunctional device It works according to its own setting 1 The device will start from digital 1 in mode s...

Страница 13: ...tor do notr otate at synchronous speedd ue to the instantaneousc hange in load Checkt he suitabilityo ft he installation water flow direction with the arrowm arko nt he pump body W aitf or thep umpt o...

Страница 14: ...2 180 50 182 232 300 8 80 OPUS D 32 12 180 2 180 50 182 232 300 8 80 PUMP TYPE D1 D2 D3 D4 D5 nx m mm L1 H1 H2 H3 H4 Weight PN6 PN10 PN6 PN10 OPUS 40 10 220 C 150 100 110 90 44 130 4x14 4x18 220 65 1...

Страница 15: ...e will be filled by the authorized DUYAR POMPA dealer from where the device was purchased and sent to DUYAR POMPA and a copy will be given to the user During the warranty period the warranty certifica...

Страница 16: ...equest is not fulfilled the seller the manufacturer and the importer are jointly and severally liable 6 The repair period of the goods cannot exceed 20 working days This period starts from the date of...

Страница 17: ...STAINLESS BOOSTER FIRE BOOSTER DNP HORIZONTAL END SUCTION PUMP SINGLE STAGE END SUCTION CLOSED WHEEL ELECTRIC OR DIESEL ENGINE AXIAL TYPE PUMP MoreDetails...

Страница 18: ...2021 11 1 WE ARE SENSIBLE TO LIVE...

Отзывы: