background image

8

OPUS 

SERIES

INSTALLATION, OPERATION, MAINTENANCE 

AND REPAIR MANUAL

In this operating mode, the pump operates by changing the rotation speed to follow a linear line between the set 

pump head (Hsetting) and half of the set value (Hsetting /2). The pump provides a head on this line depending on 

the decrease or increase in flow.

The Hsetting value of the pumps selected in accordance with the operating point is determined as follows:

► 

The H value at the operating point is marked on the variable pressure operating mode graph.

► 

If the marked point is on any operating mode curve belonging to a multiple of 0.5, the H value of that operating  

     mode curve is accepted as the Hsetting value.

► 

If the marked point is not on any operating mode curve belonging to 0.5 multiples, the closest operating mode   

    curve is passed and the H value of that curve is accepted as the Hsetting value.

The operating mode curves are plotted on the graph at 1 meter intervals. The setting can be selected on the screen 

in 0.5 meter increments.

9.4 Operating Mode Selection Criteria

  

 

The operating mode is selected by considering the criteria in the table below:

Table 9.1

Operating Mode 

Selection Criteria

Heating Systems

with Two Pipes

and Thermostatic

Valves

* Total friction loss > 4mSS

* Very long circulation line

* High friction losses

* Use of pressure balancing valve

* Extremely low branch valves

* Total friction loss < 2mSS

* Short or large diameter 

circulation lines

* Low friction losses

Single Pipe

Heating Systems

* Systems using thermostatic

valves

* Systems using thermostatic

valve and pressure balancing

valve

Underfloor 

Heating Systems

* High friction losses

* Use of pressure balancing valve

* Systems using thermostatic

valves

Table 9.1

Operating Mode 

Selection Criteria

Heating Systems

with Two Pipes

and Thermostatic

Valves

* Total friction loss > 4mSS

* Very long circulation line

* High friction losses

* Use of pressure balancing valve

* Extremely low branch valves

* Total friction loss < 2mSS

* Short or large diameter

circulation lines

* Low friction losses

Underfloor 

Heating Systems

* High friction losses

* Use of pressure balancing valve

* Systems using thermostatic

valves

Содержание OPUS 0-12 280 V

Страница 1: ...SERIES INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL OPUS...

Страница 2: ...2 OPUS SERIES INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL www duyarpompa com...

Страница 3: ...ng and Air Drain 8 6 4 Cable Fuse Selection and Electrical Installation 8 7 DISPLAY AND SETTINGS 10 7 1 Operating Modes 11 7 1 1 Manual Operating Mode 11 7 1 2 Constant Pressure Operating Mode 11 7 1...

Страница 4: ...should be as in Table 3 2 3 4 Operating Conditions OPUS circulation pumps have been developed for the circulation and pressurization of the water circulating in the heating and air conditioning system...

Страница 5: ...code Tracking Number 7 Input Voltage Voltage 8 Minimum Power 9 Minimum Current 10 Temperature Class 11 Input Frequency 12 Maximum Power 13 Maximum Current 14 Serial number 15 QR Code 16 Year of produc...

Страница 6: ...installation pressure should be between the values in Table 5 1 and Table 5 3 The pump must be operated for a while to drain the air from the installation 6 4 Cable Fuse Selection and Electrical Inst...

Страница 7: ...ichever type of pump is to be used it must be selected according to the nominal current and voltage of that pump and a B type relay which can open at DC current and high frequency Grounding current sh...

Страница 8: ...conds to set the target speed in night work When the P7 option is reached with the button when the target speed is reached with the keys by pressing the P button again the speed record is made by keep...

Страница 9: ...ng remains constant The Hsetting value of the pumps selected in accordance with the operating point is determined as follows The H value at the operating point is marked on the constant pressure opera...

Страница 10: ...selected on the screen in 0 5 meter increments 9 4 Operating Mode Selection Criteria The operating mode is selected by considering the criteria in the table below Table 9 1 Operating Mode Selection Cr...

Страница 11: ...INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL 9 10 TERMINAL CONNECTION DETAIL 10 1 Terminal Connection Detail Table 230 VAC DIN1 Communications BSM RS485 Relay Link DIN2 communication devices...

Страница 12: ...will start stop from digital 1 and from the buttons on it in Manual mode P17 DN2 selection 0 Dysfunctional device It works according to its own setting 1 The device will start from digital 1 in mode s...

Страница 13: ...tor do notr otate at synchronous speedd ue to the instantaneousc hange in load Checkt he suitabilityo ft he installation water flow direction with the arrowm arko nt he pump body W aitf or thep umpt o...

Страница 14: ...2 180 50 182 232 300 8 80 OPUS D 32 12 180 2 180 50 182 232 300 8 80 PUMP TYPE D1 D2 D3 D4 D5 nx m mm L1 H1 H2 H3 H4 Weight PN6 PN10 PN6 PN10 OPUS 40 10 220 C 150 100 110 90 44 130 4x14 4x18 220 65 1...

Страница 15: ...e will be filled by the authorized DUYAR POMPA dealer from where the device was purchased and sent to DUYAR POMPA and a copy will be given to the user During the warranty period the warranty certifica...

Страница 16: ...equest is not fulfilled the seller the manufacturer and the importer are jointly and severally liable 6 The repair period of the goods cannot exceed 20 working days This period starts from the date of...

Страница 17: ...STAINLESS BOOSTER FIRE BOOSTER DNP HORIZONTAL END SUCTION PUMP SINGLE STAGE END SUCTION CLOSED WHEEL ELECTRIC OR DIESEL ENGINE AXIAL TYPE PUMP MoreDetails...

Страница 18: ...2021 11 1 WE ARE SENSIBLE TO LIVE...

Отзывы: