Installation 2
2 - 2
Figure 2-2 Power wiring
The center terminal block position, adjacent to the letter G on the end of the I/O
module board, is chassis/ earth ground which is connected to the I/O PLEXER
case.
Standard 85-132 VAC, 47-440 Hz and option /E5 105-265 VAC 47-440Hz
Operation.
Following power wiring conventions(AWG)
Black wire to terminal marked H (hot)
White wire to the terminal marked N (neutral)
Green wire to the terminal marked G (chassis/ earth ground)
Option /B or /C 10-30 VDC Operation
+ of the power source to the terminal marked H
- of the power source to the terminal marked N
Earth Ground, where available to the terminal marked G
Digital Expander
The I/O PLEXER Digital Expander (IOP-DE) Receives its power and signals
from the I/O PLEXER via the included 24 pin keyed ribbon cable (duTec part
#CE-24) No other power wiring is required. See page 2-14
I/O Plexer Power supply
terminal block