background image

 
 

     

 

                                               02/03/16 - AC - Rev.1 

 

 

 

8/11 

5.8 MAINTENANCE PROCEDURES 

These procedures are the responsibility of maintenance operator or company authorized to conduct any revision. 
 

CAUTION:  according  to  the  current  regulations  in  the  country  where  they  are  used  fire  extinguishers,  some 
maintenance procedures may not be applicable. 

 

5.8.1 Details of maintenance procedures adopted in accordance with the regulations in force 
 

 

n. 

Phase or element checked 

 

Istructions 

Check  the  seal  and  the 
safety pin

 

Check if the seal and the safety pin have been removed.

 

Check the pressure gauge

 

Check  the  suitability  of  the  pressure  gauge.  If  it  does  not  work  freely  or  if  it 
indicates a pressure outside tolerances, check the value of the pressure inside 
the extinguisher with a control manometer pressure fitted with a grease fitting. 
If the pressure is too low, set aside the fire extinguisher and check further in the 
workshop to identify the cause.

 

Inspect the exterior of the  
extinguisher 

Check  for  signs  of  corrosion,  shock,  scratches  or  deterioration  that  could 
prevent the proper operation of the extinguisher.

 

Check the hose 

Check  the  suitability  of  the  hose  and  make  sure  it  is  level,  or  obstructed, 
fissured,  worn  or  damaged.  Blow  if  necessary  with  compressed  air.  Replace  if 
necessary. 

Check the way to use the 
extinguisher

 

Verify the accuracy and readability of the mode of use indicated on the label of 
the extinguisher.

 

Open a portable fire 
extinguisher

 

Extinguishers permanent  pressure must  be opened only in case of partial use, 
loss of pressure or weight control and possible replacement of the extinguishing 
agent. 
Open  the  portable  fire  extinguisher  conforming  to  the  safety  precautions 
described in paragraph 5.3.2, to remove the valve from the cylinder.

 

To empty a portable fire 
extinguisher

 

Pour the initial charge into a clean container and check whether the charge can 
be reused. If there is debris, replace it. Check the filter status of the float. If it is 
defective, replace the float.

 

Verify  proper  operation 
and  the  suitability  of  all 
items

 

Clean  if  necessary  and  pass  air  through  the  other  parts,  paying  particular 
attention to the valve orifice. Verify that the safety valve (if there is) and other 
parts are not blocked. Replace defective parts.  
N.B. when the pressure gauge is defective, replace the valve. 
Verify  that  the  organ  functioning  and  discharge  control  operate  freely.  Clean, 
perform  the  repair  or  replacement  of  defective  parts  if  necessary.  Protect 
moving  parts  and  threads  against  corrosion  with  a  silicone-based  lubricant 
grease.

 

Check the seals

 

Replace  the  seals.  Lubricate  the  new  seals  with  silicone  grease  before 
installation.

 

10 

Examine  the  inside  of  the 
cylinder 

Check the inside of the cylinder with a light. Verify the absence of corrosion and 
/ or deterioration of inner liner.

 

11 

Check the expiration date 
of the hydraulic test and 
replace the portable fire 
extinguisher 

Check  whether the hydraulic test  came to an end. In this case, run the test  in 
accordance  with  the  procedures  of  paragraph  5.8.3,  before  refilling  the 
extinguisher  with  the  extinguishing  agent  (water  and  additives)  or  previously 
checked  with  the  new  extinguishing  agent.  Replace  the  valve  cleaned  and 
checked with the float and the new seals lubricated on the cylinder, taking care 
to  position  them.Screw  the  valve  with  a  force  torque  as  indicated  in  the 
following  note. Pressurize the extinguisher with nitrogen  at 15 bar  (±  1 bar at  
20° C). Insert the safety pin and lock it with the new security seal. Check the seal 
of  the  valve  with  a  spray  leak  detection.  Screw  the  hose  with  the  tightening 
torque 15-20 Nm. 

Содержание 9D-34-A

Страница 1: ...this document is prohibited 02 03 16 AC Rev 1 INSTRUCTIONS USE AND MAINTENANCE PORTABLE FIRE EXTINGUISHERS WATER ADDITIVE PERMANENT PRESSURE Models 9D 58 A Class A 9D 58 A Classes A F 9D 58 AB 9D 34 A...

Страница 2: ...FIRE EXTINGUISHERS 5 5 2 GENERAL INFORMATION 6 5 3 SAFETY PRECAUTIONS FOR MAINTENANCE OPERATOR 6 5 4 RECHARGE OF THE FIRE EXTINGUISHERS 6 5 5 TAG OF MAINTENANCE 7 5 6 REVISION 7 5 7 SERVICE LIFE OF A...

Страница 3: ...a temperature not lower than 0 C and not higher than 60 C limit temperatures of use On Class B fires maintain a certain distance with the outbreaks 4 5 m to avoid liquid splashes Do not start from the...

Страница 4: ...ers It is recommended to the user or his representative to provide at regular intervals for inspection work in order to ensure that each extinguisher is located where it is indicated with a visible si...

Страница 5: ...ring 9 Valve stem assembly 10 Cylinder 11 Spring stem 12 Extinguishing agent 13 Tube holder 14 Hose 15 Dip tube 16 Label 17 Nozzle 18 Filter dip tube 19 Base Models 9D 34 A Class A 9D 34 A Classes A...

Страница 6: ...ance and charging procedures may temporarily reduce the effectiveness of preventive measures implemented at its headquarters for fire protection Therefore you must observe the following points a accor...

Страница 7: ...of revision The maintenance program is designed to make sure that portable fire extinguishers are always in working during the entire period of use All extinguishers must be subject to a revision in a...

Страница 8: ...raph 5 3 2 to remove the valve from the cylinder 7 To empty a portable fire extinguisher Pour the initial charge into a clean container and check whether the charge can be reused If there is debris re...

Страница 9: ...nguisher in accordance with the instructions of the table in paragraph 5 8 1 8 Insert a new plug and a new safety seal and fill the tag maintenance extinguisher NOTE 1 The extinguishing agent foam mus...

Страница 10: ...ring the other phases of the life time of a fire extinguisher PHASE EVENT RISK PREVENTIVE MEASURES CORRECTIVE ACTIONS TRANSPORT AND INSTALLATION Extinguisher damaged deformations due to impacts RELEAS...

Страница 11: ...ated clothing and shoes before reuse After contact with eyes In case of contact with eyes rinse promptly and thoroughly with water and seek medical advice After swallowing Remove victim from exposure...

Отзывы:

Похожие инструкции для 9D-34-A