                                               02/03/16 - AC - Rev.1 

 

 

 

7/11 

5.5 TAG OF MAINTENANCE

 

The maintenance data must be recorded on a tag that does not conceal any marking the manufacturer SAE. 
The tag contains the following data: 
- Verified / audited; 
- The recharge date specifying the nature of the extinguisher if necessary; 
- The date of additional maintenance and thorough; 
- The name and address of the specialized and enabled maintenance; 
- The signature of the service operator who has done the maintenance; 
- The date of execution of maintenance or inspection; 
- The date of revision. 
NOTE if the regulation of the country requires it, they are given the month and year of the next service. 
In addition, information concerning the details of the non-compliances identified and corrective action taken or to be 
taken to restore the proper functioning of each fire extinguisher and / or its support should be given in a document 
(registration, inspection report etc.). 
 

5.6 REVISION

 

The  service  company  verifies  that  portable  fire  extinguishers  and  restores  their  operation  must  have  specific 
equipment  and  drop  user,  statements  relating  to  the  tasks  performed.  The  service  people  should  be  qualified  to  do 
such operations. 
Normally,  such  a  company  should  implement  a  quality  system  and  be  empowered  to  conduct  the  interventions 
reviewed in accordance with the requirements of the current regulation. 

 

5.6.1 Frequency of revision: 
The maintenance program is designed to make sure that portable fire extinguishers are always in working during the 
entire period of use. 
All  extinguishers  must  be  subject  to  a  revision  in  a  specialized  and  enabled  second  intervals  the  frequency  of  which 
shall  not  be  less  than  that  established  by  current  regulations.  To  make  this  possible  to  be  implemented,  the 
maintenance man reset every year an appropriate percentage of each type of portable fire extinguisher. 
The company specializes enabled and must comply with national regulations the protection of the environment with 
regard to the disposal of extinguishing agents. 

 

5.6.2 Metod of revision: 
When a portable fire extinguisher must be subject to review, the procedure must be followed as described in the table 
in paragraph 5.8.3 and recharging must be performed in accordance with paragraph 5.4.  
 
5.6.3 Precautions in case of hydraulic test: 
In  the  event  that  water  is  used  during  the  hydraulic  test,  the  cylinders  must  be  thoroughly  dried  before  being 
recharged. 
NOTE The national regulatory or European Union on pressure vessels may be applicable for maintenance and testing of 
fire extinguishers and hydraulic cylinders, in particular, carbon dioxide and gas cartridges. 

 

5.7 SERVICE LIFE OF A PORTABLE EXTINGUISHER

 

The expected service life for a portable fire extinguisher is established by current regulations. 
It is the renponsability of the service operator, report in a written report to the user of the extinguisher, which to his 
opinion, a fire extinguisher must be eliminated. 
 

 
 
 
 
 
 
 
 

 
 

Содержание 9D-34-A

Страница 1: ...this document is prohibited 02 03 16 AC Rev 1 INSTRUCTIONS USE AND MAINTENANCE PORTABLE FIRE EXTINGUISHERS WATER ADDITIVE PERMANENT PRESSURE Models 9D 58 A Class A 9D 58 A Classes A F 9D 58 AB 9D 34 A...

Страница 2: ...FIRE EXTINGUISHERS 5 5 2 GENERAL INFORMATION 6 5 3 SAFETY PRECAUTIONS FOR MAINTENANCE OPERATOR 6 5 4 RECHARGE OF THE FIRE EXTINGUISHERS 6 5 5 TAG OF MAINTENANCE 7 5 6 REVISION 7 5 7 SERVICE LIFE OF A...

Страница 3: ...a temperature not lower than 0 C and not higher than 60 C limit temperatures of use On Class B fires maintain a certain distance with the outbreaks 4 5 m to avoid liquid splashes Do not start from the...

Страница 4: ...ers It is recommended to the user or his representative to provide at regular intervals for inspection work in order to ensure that each extinguisher is located where it is indicated with a visible si...

Страница 5: ...ring 9 Valve stem assembly 10 Cylinder 11 Spring stem 12 Extinguishing agent 13 Tube holder 14 Hose 15 Dip tube 16 Label 17 Nozzle 18 Filter dip tube 19 Base Models 9D 34 A Class A 9D 34 A Classes A...

Страница 6: ...ance and charging procedures may temporarily reduce the effectiveness of preventive measures implemented at its headquarters for fire protection Therefore you must observe the following points a accor...

Страница 7: ...of revision The maintenance program is designed to make sure that portable fire extinguishers are always in working during the entire period of use All extinguishers must be subject to a revision in a...

Страница 8: ...raph 5 3 2 to remove the valve from the cylinder 7 To empty a portable fire extinguisher Pour the initial charge into a clean container and check whether the charge can be reused If there is debris re...

Страница 9: ...nguisher in accordance with the instructions of the table in paragraph 5 8 1 8 Insert a new plug and a new safety seal and fill the tag maintenance extinguisher NOTE 1 The extinguishing agent foam mus...

Страница 10: ...ring the other phases of the life time of a fire extinguisher PHASE EVENT RISK PREVENTIVE MEASURES CORRECTIVE ACTIONS TRANSPORT AND INSTALLATION Extinguisher damaged deformations due to impacts RELEAS...

Страница 11: ...ated clothing and shoes before reuse After contact with eyes In case of contact with eyes rinse promptly and thoroughly with water and seek medical advice After swallowing Remove victim from exposure...