background image

© 2007 Duro Dyne Corporation

Printed in USA 10/2007

BI035411

DuroZone

 

SMZ-AC WIRING INSTRUCTIONS PAGE 5

SMZ-AC SYSTEM CHECKOUT PROCEDURE

The following check-out procedure requires a voltmeter set to read 24 volts A.C.. 

If, after the check-out procedure is completed, the SMZ-AC panel and dampers are operating correctly, but the system is 

not functioning properly, check your wiring carefully.  The most common problems experienced are a misplaced wire, a bad 

connection or a broken wire.  If none of these seem to be the problem, check your thermostats and equipment. 

YOU MUST 

PERFORM THE FOLLOWING TEST PROCEDURES IN THE ORDER SHOWN.  DO NOT SKIP ANY OF THESE 

STEPS. PLACE ALL DAMPER SWITCHES IN “O” (OPEN) POSITION.

1.    You must have 24 volts across R & C of the SMZ-AC Panel Equipment Terminal Strip. (This powers the SMZ-AC panel 

and your equipment).

2.    You must have 24 volts across 1 & 2 of the SMZ-AC Panel Equipment Terminal Strip, and every 1 & 2 of each SMZ-

AC Panel Zone terminal.  (This powers the dampers).

3.    To test the operation of the SMZ-AC panel, you must disconnect all thermostats.  With the thermostats disconnected, 

and 24 volts as described in #2 above, all dampers should be open. (If the dampers are not open, go to step 4).

3A . To test the heat mode, jump R to W at the SMZ-AC Panel Zone 1 Terminal Strip.  Zone 1 will be calling for heat. (All 

zone dampers, except Zone 1 will close and the furnace will turn on). The Cool Lockout Relay and Zone 1 Relay will 

activate (Red indicator light will glow).  Zone 2 or 3 can be activated by jumping W & R at the corresponding SMZ-AC 

Zone 2 or Zone 3 Terminal Strips.  If the furnace does not activate,  test for 24 volts across C & W at the SMZ-AC 

Panel Equipment Terminal Strip. If voltage reading is 24 volts, SMZ-AC panel is okay.

3B.  To test the cool mode, disconnect the R & W connections made for the heat mode check in step 3A.  Jump R &Y at the 

SMZ-AC Panel Zone 1 Terminal Strip.  Zone 1 will be calling for cooling.   (All zone dampers except zone 1 will close, 

and the air conditioning will come on.)  The Heat Lockout Relay, Equipment 1 Relay and Zone 1 Relay will activate (Red 

indicator light will glow). Zones 2 or 3 can be activated by jumping R & Y at the SMZ-AC Zone 2 or Zone 3 Terminal 

Strips.  If the air conditioning does not activate  test for 24 volts across C & Y at the SMZ-AC Panel Equipment Terminal 

Strip.  If voltage reading is 24 volts, SMZ-AC panel is okay.

3C.  To test the Fan, jump R & G at the SMZ-AC Panel Zone 1 Terminal Strip.  Be sure at least one Damper Switch is in 

“open” “(O)” position.  The fan should activate.  If the fan does not activate, with R & G jumped, test for 24 volts 

across C & G at the SMZ-AC Panel Equipment Terminal Strip.  If voltage reading is 24, panel is okay.

4.     To test the damper operation, perform step #3A, checking for 24 volts across 1 & 4 of every SMZ-AC Panel Zone 

Terminal Strip when that zone is activated, and for “O” volts at 1 & 4 of every SMZ-AC Panel Zone Terminal Strip 

that is not activated.  (IMPORTANT: This test will work only if at least one zone is activated. If no zone is activated, all 

terminal 1 & 4 readings will be 24 volts.)  If all readings are correct, the panel is operating correctly. If a damper is not 

functioning but the SMZ-AC Panel has checked out okay, check for 24 volts across terminals 1 & 2 on the damper mo-

tor. If you have 24 volts, disconnect the terminal 4 connection to the damper.  Jumping terminals 4 & 5 on the damper 

motor should make the damper open. (It will take 30 to 60 seconds for a damper to fully open.)  When you disconnect 

the jumper from terminals 4 & 5, the damper should close. If the damper tested does not operate as described, the 

problem could either be binding damper linkage, the blade movement is being obstructed, or you could have either an 

incorrect or a defective motor. (With multiblade dampers, it is possible to connect the motor to the linkage 180 “out of 

phase”, which causes the damper to be open when it should be closed, and closed when it should be open). 

Содержание DuroZone SMZ-AC

Страница 1: ... MODEL SMZ AC ZONE CONTROL SYSTEM Corporation DuroZone is a division of DuroZone DuroZone PART 35229 ...

Страница 2: ...pecial wiring for Heat Pumps Terminal O goes to changeover valve relay see special wiring for Heat Pumps Terminals 1 and 2 go to a separate 24 volt transformer used to power the Duro Zone Dampers Duro Zone s PT 40 24 volt 40VA transformer Part 35054 is recommended ZONE 1 The lower left terminal strip is for Zone 1 The Zone 1 Thermostat must have a heat cool fan on auto switchable sub base Duro Zon...

Страница 3: ...DuroZone SMZ AC WIRING INSTRUCTIONS PAGE 2 ...

Страница 4: ...DuroZone SMZ AC WIRING INSTRUCTIONS PAGE 3 ...

Страница 5: ... switch per zone These switches will allow a zone damper to remain in either the open or closed position when the system board is at rest The SMZ AC allows the installer or home owner to choose the position of his system s damp ers This feature can inhibit migration of air into spaces not desired for seasonal purposes or when a zone is not in use The SMZ AC Zone System has a built in safety featur...

Страница 6: ...Z AC Panel Zone 1 Terminal Strip Zone 1 will be calling for cooling All zone dampers except zone 1 will close and the air conditioning will come on The Heat Lockout Relay Equipment 1 Relay and Zone 1 Relay will activate Red indicator light will glow Zones 2 or 3 can be activated by jumping R Y at the SMZ AC Zone 2 or Zone 3 Terminal Strips If the air conditioning does not activate test for 24 volt...

Страница 7: ... AC La Zona 1 demandará calor Todos los dampers excepto el de la Zona 1 se cerrarán y el aire acondicionado se encenderá El relé de bloqueo de calor el relé del equipo 1 y el relé de la Zona 1 se activarán Se encenderá el indicador de la luz roja Las Zonas 2 o 3 pueden activarse realizando la desviación de R e Y en las correspondientes placas de bornes de las Zonas 2 o 3 del SMZ AC Si el aire acon...

Страница 8: ...para cada zona Estos conmutadores permitirán que el regulador de una zona permanezca en la posición abierto o cerrado cuando la placa del sistema está en reposo El sistema SMZ AC permite al instalador o propietario elegir la posición de los dampers del sistema Esta función permite inhibir la migración de aire a espacios no deseados adecuándose a las condiciones climáticas o cuando una zona no se e...

Страница 9: ...24 VAC 40 Pieza No 35054 120 VAC 120 VAC Bomba de calor Retardo de tiempo Retardo de tiempo Relé Pieza No 35055 Retardo de tiempo Pieza No 35215 Ventilador impelente NOTA La mayoría de los termostatos con R W Y y G funcionarán con este sistema en cualquier zona Los termostatos deben contar con una sub base de conmutación y o banda inactiva entre los ajustes de calor y frío ZONA 1 ZONA 3 ZONA 2 BLO...

Страница 10: ...7 con DRSHCS 35182 DRS 35187 con DRSMS 35181 3WT 35052 con MSSB 35214 TERMOSTATO DE REDUCCIÓN 35173 Calor Ventilador 120 VAC ZONA 3 ZONA 2 ZONA 1 NOTA La mayoría de los termostatos con R W Y y G funcionarán con este sistema en cualquier zona Los termostatos deben contar con una sub base de conmutación y o banda inactiva entre los ajustes de calor y frío 24 VAC Calor Compresor ZONA 1 ZONA 3 ZONA 2 ...

Страница 11: ...s para alimentar los dampers DuroZone Se recomienda el uso de un transformador PT 40 de 24 voltios 40VA Pieza No 35054 de DuroZone ZONA 1 La placa de bornes inferior izquierda es para la Zona 1 El termostato de la Zona 1 debe contar con una sub base conmutable calor frío con ventilador encendido o en modo automático Se recomienda la sub base DRSMS Pieza No 35181 de Duro Zone con un termostato DRS ...

Страница 12: ... MODELO SMZ AC SISTEMA DE CONTROL DE ZONAS Corporation DuroZone es una división de DuroZone DuroZone PIEZA N o 35229 ...

Отзывы: