E.M.6427    RELEASE 7.1  05-03 

 

6427071-230-en 8 

3. INTERFACING TO CNC 

OPERATING FUNCTIONS 

The control unit offers several operating functions (also called MODES). 
Setting MODE01, MODE02, and MODE03 signals can make the selection of the operating 
functions. 
 

INPUTS DESCRIPTION 

N° OPERATING 

FUNCTIONS 

MODE01 MODE02 MODE03 

 

0 Emergency/ 

Reset 

Setting this mode will stop immediately the turret. Alarms can 
be reset setting this mode and the setting another mode. 

1 Automatic 

shortest path 

The turret will use the shortest path to reach the position 
required. 

2 Automatic 

CW 

The turret will always use the CW direction path to reach the 
position required. 

3 Automatic 

CCW 

The turret will always use the CCW direction path to reach the 
position required. 

Jog, next tool in 
CW or CCW 

The turret will reach the next position. 

5 Service 

Enables a series of functionality to simplify the start-up phase 
and troubleshooting 

6 Maintenance 

(only by PC) 

- - - 

 

7 Safety 

Enables a series of functionality to overcome conditions that 
normally would stop the turret for a long time. 

 

ZERO SEARCH 

After any power-on of the control unit (230 V -1 phase auxiliary supply) the turret must 
execute the reference cycle. 
 

At the end of the reference cycle the turret is locked in position 1. 
To execute the reference cycle proceed as follows 
1.  Set an automatic function (1,2 or 3) 
2.  Set this code. 
 

POSITION PARITY 

PBIT01 

PBITO2 PBIT04 PBIT08 (PBIT16) 

Zero cycle 

0 0 0 0 0 0 

 
3. Set 

impulsive 

PSTART

 to reach out the zero position 

 (

PSTART 

must stay on for more than 30 ms). 

4.  Wait 500 ms after INDEXD and LOCKED signals give the end of the cycle. 

Содержание 0496006H16

Страница 1: ...2 230 12 and 24 positions DDC1 12 H20 22 0496006H20 SFW062G003 SMA 20 2 230 Std 8 12 positions DDC1 12 H20 20 0496006H20 SFW062I003 SMA 20 2 230 8 and 12 positions Compatible with SFW062E003 DDC1 12...

Страница 2: ...ION OF LOW HIGH INERTIA 6 SELECTION OF STANDARD MAINTENANCE SPEED 6 CONNECTION BOX AND TERMINALS LAY OUT 7 3 INTERFACING TO CNC 8 OPERATING FUNCTIONS 8 ZERO SEARCH 8 OPERATING FUNCTIONS DESCRIPTION 9...

Страница 3: ...dence Model DDC1 12 K20 22 Software version SFW062I003 for SM 20 IMPORTANT NOTE FOR SAFETY Do not manipulate the inside of the unit Only personnel authorized by Duplomatic may manipulate the inside of...

Страница 4: ...re unit is insulated from the external with optoinsulators to satisfy safety standards Parameters of the system are optimised and cannot be modified by the customer TECHNICAL CARACTERISTICS OF THE CON...

Страница 5: ...see tab 2 On the control unit are present two different connections 24VDC The 24VDC on terminal P10 2 is used to supply the electrovalve and must be protected with a 500 mA T fuse F5 The 24VDC on term...

Страница 6: ...ement are required Software 8 12 tools 6 12 12 24 8 16 Tools N 8 12 6 12 12 24 8 16 PTAB01 24VDC 0VDC 24VDC 0VDC 24VDC 0VDC 24VDC 0VDC PTAB02 0VDC 24VDC 0VDC 24VDC 0VDC 24VDC 0VDC 24VDC The 24VDC for...

Страница 7: ...L P10 23 EVULCK P10 4 COM 0V P10 24 SPAREOUT1 P10 5 PTABO1 LK1 CM1 P10 6 PTABO2 LK2 CM1 FUSE F1 P10 7 PTABO3 LK3 LOCKED P10 8 INDEXD P10 9 R E1 ALBIT1 P10 10 S E2 ALBIT2 P10 11 T E3 ALBIT4 P10 12 PE E...

Страница 8: ...e CCW direction path to reach the position required 4 Jog next tool in CW or CCW 0 0 1 The turret will reach the next position 5 Service 1 0 1 Enables a series of functionality to simplify the start u...

Страница 9: ...bits and parity bit must be stable for at least 30 ms from PSTART signal After this time and once the turret confirmed the start reception position bits parity bit and start signal can be changed unti...

Страница 10: ...the turret position ALARM CONDITIONS When an alarm condition is detected one or more of the ALBIT1 ALBIT2 ALBIT4 is high and the INDEXD signal is low In this case the machine must be immediately stopp...

Страница 11: ...he turret Just set the code of the position required give the start signal and the turret will automatically reach the position 1 Clear all alarms if present 2 Set an automatic function INPUTS OPERATI...

Страница 12: ...can be executed step by step unlocking rotation locking Proceed as follows 1 Clear all alarms if present 2 Set an operating function INPUTS OPERATING FUNCTION N 5 MODE01 MODE02 MODE03 Service 1 0 1 3...

Страница 13: ...of the second digit of the last alarm 5 only SW rel I 1 1 1 0 1 8 Toggle ON OFF the serialize mode 6 only SW rel I 0 0 0 1 1 9 Toggle ON OFF the output of the status of the switches 7 only SW rel I 1...

Страница 14: ...0 turret out of position 0 turret is can be locked on the position Byte 3 Digital inputs 1 In order ZEROSW ULCKSW LOCKSW MOTVL PTAB03 MOD03 MOD02 MOD01 Byte 4 Digital inputs 2 In order PTAB02 PTAB01 P...

Страница 15: ...e supply fault etc 0 1 1 6 Zero search fault switch fault setting etc 1 1 1 7 Zero search missed Position code error Cycle time out PSTART signal time out Alarm are stored and can be reset with EMERGE...

Страница 16: ...touch the piece slowly during disc rotation the wiring to the resolver is defective 33 The time limit to execute the cycle has been reached the tool touch the piece slowly at the end of the cycle so...

Страница 17: ...switch connection wiring remote application mainly the disc cannot rotate 70 A tool is called before executing the zero cycle error in programming logic of CNC the operator did not call the reference...

Страница 18: ...DUPLOMATIC E M 6427 RELEASE 7 1 05 03 6427071 230 en 18...

Страница 19: ...DUPLOMATIC E M 6427 RELEASE 7 1 05 03 6427071 230 en 19...

Страница 20: ...DUPLOMATIC E M 6427 RELEASE 7 1 05 03 6427071 230 en 20...

Страница 21: ...DUPLOMATIC E M 6427 RELEASE 7 1 05 03 6427071 230 en 21...

Страница 22: ...1 05 03 6427071 230 en 22 DUPLOMATIC AUTOMAZIONE S p A e mail 20025 LEGNANO MI ITALY P LE BOZZI 1 FAX _ 86 0512 55177725 DUPLOMATIC AUTOMAZIONE Come and visit Duplomatic homepage www hS889 com hS 889...

Отзывы: