background image

 

- 32 - 

 
 

APPLICATION DATA 

 
 

HEAT RECOVERY 

 
The Dunham-Bush Water Cooled Screw Flooded Chiller 
can significantly reduce building operating costs when the 
heat recovery option is selected. Any building which 
requires simultaneous heating and cooling may be an 
excellent candidate for this system. 

 
 

Hotter Hot Water 

Most centrifugal water chillers are limited in producing 
leaving condenser water temperatures to 105°F or below. 
Dunham-Bush Water Cooled Screw Flooded Chillers are 
able to provide leaving water temperatures over 120°F 
allowing for the installation of smaller heating coils at a 
lower first cost than systems utilizing centrifugal water 
chillers. The warmer supply air temperatures available 
will also improve tenant comfort. 

 

Greater Design Flexibility 

Centrifugal water chillers are susceptible to surge 
conditions during part-load operation and need to be 
selected to operate in a narrow operating envelope. The 
heat recovery Dunham-Bush Water Cooled Screw 
Flooded Chiller, on the other hand, utilizes a positive 
displacement compressor which will not surge. This 
chiller is capable of unloading its compressors to their 
minimum capacity at all head conditions, both cooling and 
heat recovery, for greater design flexibility. The unit can 
be modified for Heat Reclaim use. 

 

Lower Energy Consumption 

The efficient unloading characteristics of the Dunham-
Bush Water Cooled Screw Flooded Chiller compressor 
make it ideal for heat recovery duty. Heat recovery 
chillers must be selected to operate at many operating 
conditions, not just full load heating and full load cooling 
duties. Heat recovery chillers spend the majority of their 
time at lower loads, conditions at which centrifugal 
chillers must often be operating with energy inefficient hot 
gas bypass. 

 

Free Cooling Not Free Heating 

Even greater energy savings can be achieved when the 
Dunham-Bush Rotary Screw Water Cooled Heat 
Recovery Chillers are utilized to their maximum benefit. 
Typically heat recovery chillers had been thought to 
supply "free heat" while cooling a constant load within a 
building. The higher head conditions for heat recovery 
however cause the compressor to draw more power than 
for cooling only duty. The ideal way to utilize a heat 
recovery chiller would be to have it operate at only 

the capacity required for the variable-heating load. This 
would enable the remainder of the base-cooling load to 
be handled by a separate chiller utilizing evaporator 
entering condensing water temperatures and greater 
energy efficiency. Unfortunately, centrifugal chillers do 
not have the ability to operate at lower percent loads 
enabling them to satisfy only the heating load required. 
As a result, centrifugal heat recovery chillers have 
typically been operating and satisfying the base cooling 
load and utilizing only a portion of the recoverable heat to 
satisfy the variable building-heating load. Dunham-Bush 
Rotary Screw Compressor characteristics, on the other 
hand, allow the heat recovery chiller to unload to very low 
load capacities at the high head conditions created in 
heat recovery operation. To utilize the Dunham-Bush 
Rotary Screw Heat Recovery Chillers to their fullest 
potential, the designer must change his way of thinking to 
providing chillers that are unloaded to provide only the 
heating load required and simultaneously supply a portion 
of free cooling to cover the base cooling load. 

 

Controls 

Units can also be provided with optional dual controls so 
they can control leaving chilled water or leaving 
condenser water. A dual bundle condenser is provided on 
a Heat Recovery Water Chiller which minimizes space 
requirements. Consult your local Dunham-Bush Sales 
Representative for additional details. 

 

Head Pressure Control 

Cooling tower control is increasingly becoming an 
overlooked subject, and it causes problems. The 
following is a general recommendation that is applicable 
to all standard packaged chillers. 

Virtually all chiller manufacturers recommend that 
condenser water be controlled so that its temperature 
never goes below 60°F (even when the machine is off) 
and that its rate of change is not rapid. Rapid can be 
defined as not exceeding 2°F per minute. This is 
necessary because a chiller operates in a dynamic 
environment and is designed to maintain a precise 
leaving chilled water temperature under varying entering 
conditions. The additional dynamic of rapidly varying 
condenser water temperature subjects the machine to 
fluctuating pressure differentials across the evaporator 
and condenser. This varies the refrigerant flow and, 
therefore, the capacity. If this occurs faster than the 
machine can accommodate it, the head pressure or 
suction pressure will soon exceed their safety setpoints 
and the machine will shut down. 

 

 

Содержание WCFX-E Series

Страница 1: ...Products that perform By people who care WCFX E Series 60Hz Water Cooled Rotary Screw Water Chillers Cooling Capacity 70 to 1000 TR 246 to 3517 kW R134a...

Страница 2: ...atures 4 Operating Benefits 9 Typical Sequence of Operation 10 Physical Specifications 11 Dimensional Data 13 Floor Loading Diagram 19 Water Pressure Drop 20 Sound Pressure Data 26 Electrical Data 26...

Страница 3: ...inimum downtime during rework of faulty or damaged compressor Dunham Bush can arrange to provide a substitute reworked compressors while the faulty compressor is being reworked or repaired D Vapor inj...

Страница 4: ...exclusive electronically initiated hydraulically actuated control arrangement Positive Displacement Direct Connected The compressor is directly connected to the motor without any complicated gear sys...

Страница 5: ...space is decreased and the gas pressure consequently increased Discharge Phase At a point determined by the designed built in compression ratio the discharge port is covered and the compressed gas is...

Страница 6: ...hiller water temperature derivative D Evaporator Pressure D Condenser Pressure D Compressor amp draw of each compressor D Compressor elapsed run time of each compressor D Compressor starts status D Oi...

Страница 7: ...em however is very similar to centrifugal water chillers and is shown in the refrigerant cycle diagram below Liquid refrigerant enters the flooded evaporator uniformly where it absorbs heat from water...

Страница 8: ...g may be exposed to temperatures below freezing glycol protection is recommended if the water is not drained The recommended protection is 15 F below the minimum ambient temperature in the equipment r...

Страница 9: ...D ASHRAE Standard 15 Safety Code for Mechanical Refrigeration D National Electric Code D IEEE D Optional PED Refrigerant Compatibility D Designed to operate with environmentally safe and economically...

Страница 10: ...emperature is below the deadband the compressor is commanded to unload Thus the compressor capacity is continuously modulated to match applied load and hold leaving chilled water temperature at setpoi...

Страница 11: ...kW 776 6 692 8 874 3 750 9 1028 4 951 3 1162 0 1168 3 1320 6 10 4 kcal h 66 8 59 6 75 2 64 6 88 4 81 8 99 9 100 5 113 6 Min Unit Capacity 25 12 5 25 12 5 25 12 5 12 5 25 12 5 Power 460 3P 60Hz Compres...

Страница 12: ...2650 8 3080 2 3223 7 3354 2 3510 7 10 4 kcal h 204 8 201 2 210 9 219 6 228 0 264 9 277 2 288 5 301 9 Min Unit Capacity 8 5 12 5 8 5 8 5 8 5 8 5 8 5 8 5 8 5 Power 460 3P 60Hz Compressor Model Qty 1227...

Страница 13: ...630 16 7 16 417 14 7 16 366 124 1 4 3157 4 102 45 3 16 1148 5 127 6 152 WCFX E 15S 2 1 16 53 16 7 8 429 101 7 8 2588 6 153 1 9 16 39 12 3 8 315 5 5 8 143 83 1 4 2115 28 1 8 715 18 3 16 462 15 3 8 391...

Страница 14: ...530 164 3 16 4171 11 16 17 3 1 2 89 6 7 8 175 15 7 8 403 22 5 16 567 30 3 4 782 5 5 8 143 70 1778 6 152 8 203 WCFX E 30S 20 508 40 11 16 1033 40 11 16 1033 40 11 16 1033 25 635 58 1 2 1486 53 1 2 135...

Страница 15: ...3 16 3866 29 1 4 743 5 5 8 143 5 5 8 143 5 5 8 143 5 5 8 143 19 3 16 487 20 3 16 513 15 1 4 387 15 1 4 387 15 1 4 387 5 5 8 143 6 7 8 175 6 7 8 175 12 5 8 321 12 5 8 321 12 7 8 327 18 1 4 464 78 7 8 2...

Страница 16: ...64 1 2 1638 64 1 2 1638 86 11 16 2202 7 8 22 1 7 8 48 18 15 16 480 196 3 4 4997 1 1 2 38 3 7 8 99 8 5 8 219 20 508 28 5 16 719 39 11 16 1008 7 3 8 187 80 2032 10 254 10 254 WCFX E 60T 15 381 55 1397...

Страница 17: ...2057 86 2184 7 8 22 1 7 8 48 20 5 8 524 213 3 4 5429 1 1 2 38 4 1 4 108 10 3 16 259 25 1 2 648 27 5 16 694 41 1 2 1055 8 1 8 207 88 2235 12 305 12 305 WCFX E 84 15 381 60 11 16 1541 60 11 16 1541 60...

Страница 18: ...1 11 16 1312 10 3 4 273 99 2515 14 356 14 356 WCFX E 118 20 508 52 7 16 1331 52 7 16 1331 52 7 16 1331 27 686 72 5 8 1845 72 5 8 1845 129 9 16 3291 7 8 22 1 7 8 48 17 7 8 454 199 5055 1 1 2 38 3 1 2 8...

Страница 19: ...50T 2521 1144 3385 1536 2403 1090 3181 1443 2285 1036 2976 1350 2166 983 2771 1257 21688 9837 54T 2696 1223 3713 1684 2579 1170 3489 1583 2461 1116 3265 1481 2343 1063 3041 1380 23588 10699 57T 2811...

Страница 20: ...6T 1 10 100 1000 10000 Pressure Drop ft wg Water Flow Rate USgpm 1 10 100 100 1000 10000 Pressure Drop ft wg Water Flow Rate USgpm 46T 50T 73T 75T 81T 54T 57T 60T 20T 22T 24T 27T 30T 38T 40T 20T 22T 2...

Страница 21: ...ate USgpm WATER PRESSURE DROP IMPERIAL UNITS 1C EVAPORATOR 3 PASS a Single Compressor b Twin Compressors c Three Compressors 2A CONDENSER 1 PASS a Single Compressor b Twin Compressors c Three Compress...

Страница 22: ...Rate USgpm WATER PRESSURE DROP IMPERIAL UNITS 2B CONDENSER 2 PASS a Single Compressor b Twin Compressors c Three Compressors 2C CONDENSER 3 PASS a Single Compressor b Twin Compressors c Three Compress...

Страница 23: ...10 100 1000 100 1000 10000 Pressure Drop kPa Water Flow Rate m hr 57T 60T 73T 75T 81T 10 100 100 1000 10000 Pressure Drop kPa Water Flow Rate m hr 20T 22T 24T 40T 38T 27T 30T 54T 50T 46T 40T 20T 22T 2...

Страница 24: ...WATER PRESSURE DROP SI UNITS 1C EVAPORATOR 3 PASS a Single Compressor b Twin Compressors c Three Compressors 2A CONDENSER 1 PASS a Single Compressor b Twin Compressors c Three Compressors Note Above...

Страница 25: ...ER PRESSURE DROP SI UNITS 2B CONDENSER 2 PASS a Single Compressor b Twin Compressors c Three Compressors 2C CONDENSER 3 PASS a Single Compressor b Twin Compressors c Three Compressors Note Above water...

Страница 26: ...0 408 3 612 4 20S 460VAC 10 400 200 1222 1 154 499 749 20T 460VAC 10 300 200 1210 2 78 0 2 283 0 2 424 5 2 22T 460VAC 10 400 200 1210 1 1212 1 78 0 104 0 283 0 392 0 424 5 588 0 23S 460VAC 10 400 200...

Страница 27: ...27 TYPICAL WIRING SCHEMATIC Two Compressors Unit...

Страница 28: ...28 TYPICAL WIRING SCHEMATIC...

Страница 29: ...29 TYPICAL WIRING SCHEMATIC...

Страница 30: ...30 TYPICAL WIRING SCHEMATIC...

Страница 31: ...31 TYPICAL WIRING SCHEMATIC...

Страница 32: ...only the capacity required for the variable heating load This would enable the remainder of the base cooling load to be handled by a separate chiller utilizing evaporator entering condensing water tem...

Страница 33: ...e point floating or tri state control and the analog can be used to drive a 0 10 vdc actuator Thus even though there has been a trend toward fan cycling control of cooling towers it is not a device th...

Страница 34: ...ages can be controlled via an Equipment Management Center D Unit mounted disconnect switch 400 to 575 volts applications D Flanged semi hermetic compressor D Discharge service valve for MSC 226 series...

Страница 35: ...ompressor loading based on leaving chilled water temperature It shall provide for high and low refrigerant pressure protection low oil level protection evaporator water freeze protection sensor error...

Страница 36: ......

Отзывы: