7.0 

System Tests 

 

7.1 

Input the times from this table to ensure Smart -Vent is working correctly. Replace the outside temperature  

 

sensor with a potentiometer to simulate outside air temperature. 

 

(NOTE: Smart-Vent should be to powered off during air sensor change-over). 

 
7.2 

Adjust the following settings to carry out the required test: 

 

OAT   

 

Outside Air Temperature; adjust using the potentiometer 

 

PP 

 

 

Pre-Purge; enabled using the switch 

 

DTFC  

 

Daytime Free-Cooling; enabled using the switch 

 

NTFC  

 

Night-time Free-Cooling; enabled using the switch 

 

CO

   

 

Use a CO

 spray or breathe on the sensor on Smart-Vector room controller 

 

SETPOINT   

Adjust on the Smart Vector Controller 

 

Test 

Time 

SETTINGS 

Expected Results 

OAT 

Pre-Purge 

DTFC 

NTFC 

CO

 

SETPOINT 

Fan(s) 

Damper 

Pre-Purge 

05:28 

MID 

ON 

OFF 

OFF 

LOW 

MID 

OFF 

CLOSED 

05:32 

MID 

ON 

OFF 

OFF 

LOW 

MID 

ON 

OPEN 

05:45 

MID 

OFF 

OFF 

OFF 

LOW 

MID 

OFF 

CLOSED 

DTFC 

05:45 

MID 

OFF 

ON 

OFF 

LOW 

LOW 

OFF 

CLOSED 

06:15 

MID 

OFF 

ON 

OFF 

LOW 

LOW 

ON 

OPEN 

06:15 

MID 

OFF 

OFF 

OFF 

LOW 

LOW 

OFF 

CLOSED 

06:15 

MID 

OFF 

ON 

OFF 

LOW 

HIGH 

OFF 

CLOSED 

NTFC 

17:15 

MID 

OFF 

OFF 

ON 

LOW 

LOW 

OFF 

CLOSED 

18:15 

MID 

OFF 

OFF 

ON 

LOW 

LOW 

ON 

OPEN 

18:15 

MID 

OFF 

OFF 

OFF 

LOW 

LOW 

OFF 

CLOSED 

18:15 

MID 

OFF 

OFF 

ON 

LOW 

HIGH 

OFF 

CLOSED 

CO

 

06:15 

MID 

OFF 

OFF 

OFF 

LOW 

MID 

OFF 

CLOSED 

06:15 

MID 

OFF 

OFF 

OFF 

HIGH 

MID 

ON 

OPEN 

OAT 

05:32 

LOW 

ON 

ON 

ON 

LOW 

MID 

OFF 

CLOSED 

06:15 

LOW 

ON 

ON 

ON 

LOW 

MID 

OFF 

CLOSED 

18:15 

LOW 

ON 

ON 

ON 

LOW 

MID 

OFF 

CLOSED 

06:15 

LOW 

ON 

ON 

ON 

HIGH 

MID 

ON 

OPEN 

Note: 
i) 

Where the OAT is Low it requires to be less than 10°C 

ii) 

Tests above assume day time (occupied) times are 06:00 

– 18:00, adjust to suite timeclock schedule 

iii) 

Reconnect outside air sensor when tests are complete 

iv) 

Return timeclock schedule to its desired settings 

 

SPARES/SERVICE 
PLEASE WRITE THE DETAILS OF THE UNIT HERE. 
These details will be required when ordering spares for you Dunham-Bush Smart-Vector network panel 
 
UNIT TYPE AND MODEL INFORMATION 
 
                                                                                                                                                              
SERIAL NUMBER 
 
                                                                                                                                                              
DATE OF INSTALLATION 
 
                                                                                                                                                              
Spare parts/service – Please contact our office, contact information shown on page 1 
Manufacturer reserves the right to change any product specification without notice 
 

Содержание Smart-Vent

Страница 1: ...is ordered and supplied as a separate accessory to Smart Vector room units and includes an external air temperature sensor supplied loose for installation and wiring on site Diagram 1 Smart Vent netwo...

Страница 2: ...Page 2 of 8 Diagram 2 Smart Vent network panel dimensions and weight...

Страница 3: ...The panel can be fixed to a vertical wall surface using normal fixings that are suitable for wall construction 3 2 It is recommended that the panel is sited between 1 0 1 5m above floor level in a loc...

Страница 4: ...Page 4 of 8 Diagram 3 Typical wiring diagram for Smart Vent network panel NOTE ALWAYS USE WIRING DIAGRAM ENCLOSED WITH THE PANEL...

Страница 5: ...isplay numbered 1 to 8 See diagram 4 A switch is on in the up position 4 4 Switch nos 1 5 are used to set the network address switch no 6 is not used switch nos 7 and 8 are used to set the baud rate a...

Страница 6: ...settings Baud rate is 19200 Modbus address is 100 If required select the setting and enter these settings 5 5 Select Return to return to Main Screen 5 6 Select the calendar icon to enter the Calendar...

Страница 7: ...are run at full speed for 30 minutes prior to start of daytime occupied schedule On all Smart Vector units the fresh air dampers fully open and fans run to purge treated spaces with fresh air Individ...

Страница 8: ...W ON OPEN 06 15 MID OFF OFF OFF LOW LOW OFF CLOSED 06 15 MID OFF ON OFF LOW HIGH OFF CLOSED NTFC 17 15 MID OFF OFF ON LOW LOW OFF CLOSED 18 15 MID OFF OFF ON LOW LOW ON OPEN 18 15 MID OFF OFF OFF LOW...

Отзывы: