Configuring Smart-Vector Room Controllers 

 

 

 

 

 

Diagram 4: Smart-Vector Room Controller fascia   

Diagram 5: Location of binary “bit” switches 

 
 
4.1 

Before Smart-Vent network panel can be used, each room controller must be configured with a network  

 

address, using the binary “bit-switches” on each room controller.  A maximum of 20 addresses can be  

 

configured with the switches. 

 
4.2 

Carefully remove the room controller fascia, by prising and unclipping it from the bottom. 

 
4.3 

The binary switches are located below the controller display, numbered 1 to 8 (See diagram 4). A switch is on 

 

in the “up” position. 

 
4.4 

Switch nos. 1-5 are used to set the network address; switch no. 6 is not used; switch nos. 7 and 8 are used to 

 

set the baud rate at 19200 

 
4.5 

Set the network address (room or controller number) and the baud rate using the table below 

 

S

w

itc

h No

B

in

ar

V

al

ue

 

N

et

w

or

Room / Controller No. 

10 

11 

12 

13 

14 

15 

16 

17 

18 

19 

20 

S

et

 al

l s

w

itc

he

of

ON 

 

ON 

 

ON 

 

ON 

 

ON 

 

ON 

 

ON 

 

ON 

 

ON 

 

ON 

 

 

ON  ON 

 

 

ON  ON 

 

 

ON  ON 

 

 

ON  ON 

 

 

ON  ON 

 

 

 

 

ON  ON  ON  ON 

 

 

 

 

ON  ON  ON  ON 

 

 

 

 

ON 

 

 

 

 

 

 

 

ON  ON  ON  ON  ON  ON  ON  ON 

 

 

 

 

 

16 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON  ON  ON  ON  ON 

32 

Switch Not  Used 

n/a 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n/a 

ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON  ON 

 
 
4.6 

When switches are set, replace the room controller cover. 

 

 

Содержание Smart-Vent

Страница 1: ...is ordered and supplied as a separate accessory to Smart Vector room units and includes an external air temperature sensor supplied loose for installation and wiring on site Diagram 1 Smart Vent netwo...

Страница 2: ...Page 2 of 8 Diagram 2 Smart Vent network panel dimensions and weight...

Страница 3: ...The panel can be fixed to a vertical wall surface using normal fixings that are suitable for wall construction 3 2 It is recommended that the panel is sited between 1 0 1 5m above floor level in a loc...

Страница 4: ...Page 4 of 8 Diagram 3 Typical wiring diagram for Smart Vent network panel NOTE ALWAYS USE WIRING DIAGRAM ENCLOSED WITH THE PANEL...

Страница 5: ...isplay numbered 1 to 8 See diagram 4 A switch is on in the up position 4 4 Switch nos 1 5 are used to set the network address switch no 6 is not used switch nos 7 and 8 are used to set the baud rate a...

Страница 6: ...settings Baud rate is 19200 Modbus address is 100 If required select the setting and enter these settings 5 5 Select Return to return to Main Screen 5 6 Select the calendar icon to enter the Calendar...

Страница 7: ...are run at full speed for 30 minutes prior to start of daytime occupied schedule On all Smart Vector units the fresh air dampers fully open and fans run to purge treated spaces with fresh air Individ...

Страница 8: ...W ON OPEN 06 15 MID OFF OFF OFF LOW LOW OFF CLOSED 06 15 MID OFF ON OFF LOW HIGH OFF CLOSED NTFC 17 15 MID OFF OFF ON LOW LOW OFF CLOSED 18 15 MID OFF OFF ON LOW LOW ON OPEN 18 15 MID OFF OFF OFF LOW...

Отзывы: