Setting Day Time (Occupied) and Night Time Schedules 

 
5.1 

Timeclock schedules for day and night time can be set via 3.5”   touchscreen 

 

display. The Main Screen is shown in Diagram 6. 

 
5.2 

Select the room temperature display to enter the Menu Screen 

 

(See Diagram 9). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
5.3 

Select the gearwheel icon at the bottom of the screen to enter Admin  

 

Settings Screen (Diagram 7). Select System Menu enter the password  

 

as requested (default 6666) 

 
5.4 

Check the following settings 

 

 

Baud rate is 19200 

 

 

Modbus address is 100 

 

If required, select the setting and enter these settings. 

 
5.5 

Select Return to return to Main Screen 

 
 
 
 
 
 
 
 
 
5.6 

Select the calendar icon to enter the Calendar Schedule 

 
5.7 

Select the first day and set the times that rooms are to be occupied. 

 
5.8 

To copy the occupied times to another day, select Copy and the 

 

source day to be copied. The source day will highlight in red. 

 
5.9 

Select the target days which will highlight in white. 

 
5.10  Select Copy again to copy the occupied times to the required days. 
 
5.11  Select Return to return the Main Screen. 
 
 

 

Diagram 6: Home Screen 
 
 

 

Diagram 7: Admin 
Settings  
 
 

 

Diagram 8: Calendar 
Schedule 
 

 
 

 

 

Содержание Smart-Vent

Страница 1: ...is ordered and supplied as a separate accessory to Smart Vector room units and includes an external air temperature sensor supplied loose for installation and wiring on site Diagram 1 Smart Vent netwo...

Страница 2: ...Page 2 of 8 Diagram 2 Smart Vent network panel dimensions and weight...

Страница 3: ...The panel can be fixed to a vertical wall surface using normal fixings that are suitable for wall construction 3 2 It is recommended that the panel is sited between 1 0 1 5m above floor level in a loc...

Страница 4: ...Page 4 of 8 Diagram 3 Typical wiring diagram for Smart Vent network panel NOTE ALWAYS USE WIRING DIAGRAM ENCLOSED WITH THE PANEL...

Страница 5: ...isplay numbered 1 to 8 See diagram 4 A switch is on in the up position 4 4 Switch nos 1 5 are used to set the network address switch no 6 is not used switch nos 7 and 8 are used to set the baud rate a...

Страница 6: ...settings Baud rate is 19200 Modbus address is 100 If required select the setting and enter these settings 5 5 Select Return to return to Main Screen 5 6 Select the calendar icon to enter the Calendar...

Страница 7: ...are run at full speed for 30 minutes prior to start of daytime occupied schedule On all Smart Vector units the fresh air dampers fully open and fans run to purge treated spaces with fresh air Individ...

Страница 8: ...W ON OPEN 06 15 MID OFF OFF OFF LOW LOW OFF CLOSED 06 15 MID OFF ON OFF LOW HIGH OFF CLOSED NTFC 17 15 MID OFF OFF ON LOW LOW OFF CLOSED 18 15 MID OFF OFF ON LOW LOW ON OPEN 18 15 MID OFF OFF OFF LOW...

Отзывы: