Dunham-Bush Smart-Vent Скачать руководство пользователя страница 7

 

 

Page 7 of 8 

 

5.0 

Setting Day Time (Occupied) and Night Time Schedules cont. 

 
5.12  To change the system date and time, select the clock icon. 
 
5.13  Check and revise the system date and time. 
 
5.14  Select the Return button to return to the Main Screen. 
 
5.15  To clean the touchscreen, select Clean Screen. The touchscreen will be  
 

disabled for 30 seconds to allow the screen to be cleaned. 

 
5.16  Diagram 9 shows the Menu Screen and relevant icons. 
 
 
 

 

Diagram 9: Menu Screen 
 

 
 
6.0 

User Controls 

 
6.1 

User controls allow the day time (occupied) and night time settings to be  

 

overridden, using the controls described below. 

 
6.2 

Timeclock Override Button

 

 

This button enables the daytime schedule to be extended up to five hours.  

 

Press the button to cycle through the override periods (1h, 2h, 3h, 4h, 5h).  

 

A green LED will indicate the selected override period; to return to  

 

normal timeclock schedule, press the button to cycle through the periods  

 

until no LED is lit. 

 
6.3 

Pre-Purge Switch

 

When enabled, all Smart-Vector units are run at full speed for 30 minutes  

 

prior to start of daytime (occupied) schedule. On all Smart-Vector units, the  

 

fresh air dampers fully open and fans run to purge treated spaces with fresh  

 

air. Individual units are fitted with frost protection thermostats, which may  

 

override fresh air dampers to circulate room air only 

 
6.4 

Day Time (Occupied) Cooling mode

 

 

When enabled, all Smart-Vector units  will provide “free-cooling” by running  

 

at full speed with fresh air dampers open, if room air temperature is more  

 

than 1K above outside air temperature 

and

 above temperature setpoint. 

 

Timeclock schedule for day time is user-programmable via the touch screen   

 

and room temperature setpoint is user-adjustable via Smart-Vent room  

 

controllers, with +/- 3K user adjustment 

 
6.5 

Night Time Cooling mode

 

 

When enabled, all Smart-Vector units will provide “free-cooling” by running at  

 

full speed with fresh air dampers open, if room air temperature is more than  

 

1K above outside air temperature. Timeclock schedule for night time is 

 

user-programmable via the touch screen and room temperature setpoint is  

 

user-adjustable via Smart-Vent room controllers, with +/- 3K user  

 

adjustment.  

 

Diagram 10: Timeclock 
Override Button 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание Smart-Vent

Страница 1: ...is ordered and supplied as a separate accessory to Smart Vector room units and includes an external air temperature sensor supplied loose for installation and wiring on site Diagram 1 Smart Vent netwo...

Страница 2: ...Page 2 of 8 Diagram 2 Smart Vent network panel dimensions and weight...

Страница 3: ...The panel can be fixed to a vertical wall surface using normal fixings that are suitable for wall construction 3 2 It is recommended that the panel is sited between 1 0 1 5m above floor level in a loc...

Страница 4: ...Page 4 of 8 Diagram 3 Typical wiring diagram for Smart Vent network panel NOTE ALWAYS USE WIRING DIAGRAM ENCLOSED WITH THE PANEL...

Страница 5: ...isplay numbered 1 to 8 See diagram 4 A switch is on in the up position 4 4 Switch nos 1 5 are used to set the network address switch no 6 is not used switch nos 7 and 8 are used to set the baud rate a...

Страница 6: ...settings Baud rate is 19200 Modbus address is 100 If required select the setting and enter these settings 5 5 Select Return to return to Main Screen 5 6 Select the calendar icon to enter the Calendar...

Страница 7: ...are run at full speed for 30 minutes prior to start of daytime occupied schedule On all Smart Vector units the fresh air dampers fully open and fans run to purge treated spaces with fresh air Individ...

Страница 8: ...W ON OPEN 06 15 MID OFF OFF OFF LOW LOW OFF CLOSED 06 15 MID OFF ON OFF LOW HIGH OFF CLOSED NTFC 17 15 MID OFF OFF ON LOW LOW OFF CLOSED 18 15 MID OFF OFF ON LOW LOW ON OPEN 18 15 MID OFF OFF OFF LOW...

Отзывы: