Smart-Vent 

 

Network Panel IOM Instructions 

Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD 

Document Ref: 

023 9247 7700    

[email protected] 

121-000-015-B 

UK:www.dunham-bush.co.uk 

Global:www.dunham-bush.com 

March 2020 

 

Page 1 of 8 

 

INSTALLER: Please leave these instructions, wiring diagram & access panel keys with the user. 

 
1.0 

Introduction 

 
1.1 

This booklet provides guidance to identify, handle, install, commission, operate and maintain Dunham-Bush  

 

Smart-Vent network panel. The instructions apply to the standard panel only. 

 

Please study the instructions carefully before commencing any installation work. 

 
1.2 

The Smart-Vent network panel is supplied as a single item, to enable complete system control of Smart-Vector 

 

units. It is ordered and supplied as a separate accessory to Smart-Vector room units and includes an external 

 

air temperature sensor, supplied loose for installation and wiring on-site. 

 
 
 

 

 Diagram 1: Smart-Vent network panel. 

1.3 

The panel is fitted with: 

 

a) touch-screen user control of timeclock  

 

     schedule settings 

 

b) timeclock override button with 1, 2, 3, 4 and  

 

    5 hour options 

 

c) Pre-Purge enable switch 

 

d) Day Time Cooling enable switch 

 

e) Night Time Cooling enable switch 

 
1.4 

Smart-Vent should be connected to individual  

 

Smart-Vector master units via their room controllers 

 

by a single cable using RS485 polarity dependent 

 

protocol. 

 
1.5 

When operating, Smart-Vent control will override all 

 

the control strategy on individual Smart-Vector room 

 

controllers. 

 
1.6 

If the Smart-Vent controller is disabled, disconnected 

 

or switched off, Smart-Vector units will continue to 

 

operate as stand-alone  units, with their room 

 

controller strategies  

 

activated 

 
 

Содержание Smart-Vent

Страница 1: ...is ordered and supplied as a separate accessory to Smart Vector room units and includes an external air temperature sensor supplied loose for installation and wiring on site Diagram 1 Smart Vent netwo...

Страница 2: ...Page 2 of 8 Diagram 2 Smart Vent network panel dimensions and weight...

Страница 3: ...The panel can be fixed to a vertical wall surface using normal fixings that are suitable for wall construction 3 2 It is recommended that the panel is sited between 1 0 1 5m above floor level in a loc...

Страница 4: ...Page 4 of 8 Diagram 3 Typical wiring diagram for Smart Vent network panel NOTE ALWAYS USE WIRING DIAGRAM ENCLOSED WITH THE PANEL...

Страница 5: ...isplay numbered 1 to 8 See diagram 4 A switch is on in the up position 4 4 Switch nos 1 5 are used to set the network address switch no 6 is not used switch nos 7 and 8 are used to set the baud rate a...

Страница 6: ...settings Baud rate is 19200 Modbus address is 100 If required select the setting and enter these settings 5 5 Select Return to return to Main Screen 5 6 Select the calendar icon to enter the Calendar...

Страница 7: ...are run at full speed for 30 minutes prior to start of daytime occupied schedule On all Smart Vector units the fresh air dampers fully open and fans run to purge treated spaces with fresh air Individ...

Страница 8: ...W ON OPEN 06 15 MID OFF OFF OFF LOW LOW OFF CLOSED 06 15 MID OFF ON OFF LOW HIGH OFF CLOSED NTFC 17 15 MID OFF OFF ON LOW LOW OFF CLOSED 18 15 MID OFF OFF ON LOW LOW ON OPEN 18 15 MID OFF OFF OFF LOW...

Отзывы: