EVAPORATOR WATER PRESSURE DROP
MODEL HRSC-D
CHILLER MODEL
CURVE NO.
MIN. GPM
MAX. GPM
50
CHS008601B*
1
70
242
60
CHS010601B*
2
78
316
75
CHS011601B*
3
85
316
100
CHD013601B*
4
100
420
110, 120
EXD12102J07DVTO
5
160
444
135, 150
EXD14102J07DVTO
6
175
553
180, 220, 225
EXT18122J07DFRO
7
270
1060
240, 255, 270, 300
EXT20122J07DFRO
8
300
1140
*These chillers have welded heads. All other chillers have removable heads.
NOTE: Constant water flow through the evaporator is required with a minimum of three gallons per
ton of system water loop volume. System volume should increase
up to ten gallons per ton for process loads, low load applications with small
temperature ranges, or systems with widely fluctuating loads.