CAPACITY CONTROL
Each compressor can modulate from 100% to 30% of full
load by slide valve operation. This provides reduction down
to 7.5% on four-compressor units.
Further reduction is possible on all units through use of
the hot gas bypass option which reduces compressor capac-
ity to 10%. Minimum capacities are tabulated below.
Model Number
HRSC
50-75
HRSC 100-150
HRSC 180-225
HRSC
240 300
Circuits
1
2
3
4
Standard Min.
Unloading
30%
15%
10%
7.5%
Optional Hot
Gas Bypass
15%
7.5%
5%
4%
PHYSICAL DATA
MODELS HRSC-50 THRU 150
Model HRSC
50
60
75
100
110
120
135
150
Nominal Capacity - Tons
40
50
60
80
85
95
110
120
No. of Compressors
1
1
1
2
2
2
2
2
Nominal Size (HP)
50
60
75
(2)50
50-60
(2)60
60-75
(2)75
Oil Charge (Oz./Compr)
202
236
236
(2)202
(1)202(1)236
(2)236
(2)236
(2)236
Crankcase Heater (Watts)
200
200
200
(2)200
(2)200
(2)200
(2)200
(2)200
Storage Capacity (Gal.)
6.25
9.4
11.1
17.6
25.4
25.4
29.4
29.4
Diameter x Length
860
1060
1160
1360
12102
12102
4102
14102
No. of SPD-SD Condensers
1
1
1
1
1
1
1
1
SPD-SD Condenser Size
70
70
70
140
140
140
140
140
Refrigerant Charge - R22 (lbs.)(1)
96
130
156
208
228
247
280
312
HRSC Operating Weight (lbs.)(2)
1700
2100
2325
3240
3555
4590
5415
5910
SEMI-HERMETIC SCREW TYPE COMPRESSORS
COOLER
REMOTE CONDENSER
UNIT
MODELS HRSC-180 THRU 300
Model HRSC
180
210
225
240
255
270
300
Nominal Capacity - Tons
145
165
175
190
205
210
230
SEMI-HERMETIC SCREW TYPE COMPRESSORS
No. of Compressors
3
3
3
4
4
4
4
Nominal Size (HP)
(3)60
(1)60(2)75
(3)75
(4)60
(3)60(1)75
(2)60(2)75
(4)75
Oil Charge (Oz./Compr)
(3)236
(3)236
(3)236
(4)236
(4)236
(4)236
(4)236
Crankcase Heater (Watts)
(3)200
(3)200
(3)200
(4)200
(4)200
(4)200
(4)200
COOLER
Storage Capacity (Gal.)
60.5
60.5
60.5
67.7
67.7
67.7
67.7
Diameter x Length
18122
18122
18122
20122
20122
20122
20122
REMOTE CONDENSER
No. of SPD-SD Condensers
1/1
1/1
1/1
2
2
2
2
SPD-SD Condenser Size
70/140
70/140
70/140
140
140
140
140
UNIT
Refrigerant Charge - R22 (lbs.)(1)
390
442
481
546
575
611
663
HRSC Operating Weight (lbs.)(2)
8710
8860
8950
10460
10560
10650
10800
NOTES:
1.
Refrigerant charge includes condenser but does not include refrigerant piping.
2.
HRSC operating weight does not include remote condenser. See page 12 for condenser weights.
24
Содержание HRSC - D
Страница 20: ...19 TYPICAL HRSC 150 POWER WIRING 460 3 60 COMPRESSOR MOTORS 1 2 SEE NOTE 5...
Страница 21: ...20 TYPICAL HRSC 150 CONTROL WIRING Electrical Mechanical...
Страница 22: ...21 TYPICAL HRSC 150 CONTROL WIRING Optional Micro Computer Controller...
Страница 23: ......
Страница 29: ......
Страница 30: ......