
68 … 76
MC • Edition 2022.08 • No
. 279 663 R
ev
. -0
14.5 SAV Leakage test
14.6 Recommended maintenance intervals
Max. inlet pressure [bar]
Functional test
Maintenance
> 0.1 to 1
every 4 years
every 8 years
> 1 to 5
every 2 years
every 4 years
> 5
once a year
every 2 years
Go to section "12. Commissioning, decomissioning
and recommissioning for FRM-NOC or SAV" for per-
forming functional and leakage testing of SAV.
1. The maintenance intervals depend on the system-
specific operating and environmental conditions, gas
quality, state of the pipelines, etc.
2. The maintenance intervals have to be set by the sys
-
tem operator according to the system requirements.
3. It is recommended to perform a functional test on a
monthly base and carry out maintenance works every
year including a leakage testing, in order to guarantee
the system availability.
4. It is necessary to comply at least with the maintenance
intervals specified in G 495.
Содержание FRM-NOC 100025 HD
Страница 17: ...MC Edition 2022 08 No 279 663 Rev 0 17 76 A B C D E A B C D E F Type UHD F Type HD...
Страница 45: ...MC Edition 2022 08 No 279 663 Rev 0 45 76 Type UHD X Y Q S W V M C A B D E G F J K L N P H O R U I...
Страница 47: ...MC Edition 2022 08 No 279 663 Rev 0 47 76 Type ND MD for 2 DN 40 DN 50 M B D E G F J K L N H X Y Q S W V O I T...
Страница 66: ...66 76 MC Edition 2022 08 No 279 663 Rev 0 14 4 Tools required A B C2 D C1...
Страница 74: ...74 76 MC Edition 2022 08 No 279 663 Rev 0...
Страница 75: ...MC Edition 2022 08 No 279 663 Rev 0 75 76...