26 … 76
MC • Edition 2022.08 • No
. 279 663 R
ev
. -0
27 … 76
10. Function Safety Shut off Valve (SAV+ASE)
SAV protects downstream fittings or lines against pres
-
sures that are too high or too low. As soon as the pre-set
trip pressure falls below or exceeds a limit due to a fault,
the SAV automatically interupts the gas flow. Under normal
operating condition the SAV is open.
If the equipment downstream of the regulator, including
any pipework, cannot safely operate or contain a pressure
equal to the highest supply pressure (inlet to regulator), a
SAV must be installed. The SAV is designed to shut down
the gas supply in the event of a fault condition.
The SAV complies with the requirements of EN 14382 as
safety shutoff valve.
Main components
A Valve disc
B Closing spring
C Ball catch / trigger mechanism
D Chamber with the pressure to be monitored
E Working diaphragm
F Push rod
G Setpoint spring for p
do
H Setpoint spring for p
du
I Protective cap
Function
Chamber D is connected to the outlet pressure via a
pulse line.
The pressure to be controlled acts on the working mem
-
brane E. The force of the set point springs G
and
H acts
as a counter force.
In case of an unbalance of forces (overpressure or un
-
derpressure), the SAV is actuated and the gas supply is
blocked.
A
B
C
D
E
F
G
H
I
Содержание FRM-NOC 100025 HD
Страница 17: ...MC Edition 2022 08 No 279 663 Rev 0 17 76 A B C D E A B C D E F Type UHD F Type HD...
Страница 45: ...MC Edition 2022 08 No 279 663 Rev 0 45 76 Type UHD X Y Q S W V M C A B D E G F J K L N P H O R U I...
Страница 47: ...MC Edition 2022 08 No 279 663 Rev 0 47 76 Type ND MD for 2 DN 40 DN 50 M B D E G F J K L N H X Y Q S W V O I T...
Страница 66: ...66 76 MC Edition 2022 08 No 279 663 Rev 0 14 4 Tools required A B C2 D C1...
Страница 74: ...74 76 MC Edition 2022 08 No 279 663 Rev 0...
Страница 75: ...MC Edition 2022 08 No 279 663 Rev 0 75 76...