12.4 Recommissioning
12.5 Decommissioning
1. Close the shutoff valve upstream of the bypass.
2. Remove the hose.
3. Open the ball valve upstream of SBV.
1. Slowly close the shutoff valve on the outlet side.
2. Slowly close the shutoff valve on the inlet side.
13. Faults and related causes
Fault on SAV
Possible causes
Troubleshooting
It is not possible to open/
activate the SAV.
The impulse line is not installed.
Install the impulse line.
The impulse line is clogged.
Clean the impulse line.
The impulse line is leaky.
Seal the impulse line.
The impulse line is broken.
Replace the impulse line.
The impulse pressure is outside the adjustment range.
Set the shut-down pressure of the SAV or the
outlet pressure.
The adjusting springs are not suitable for the application.
Replace the adjusting springs.
The adjustment range of the SAV is outside the outlet pressure.
Replace the SAV or the ASE.
The SAV cannot be acti
-
vated.
The impulse line is not installed.
Connect/install the pulse line.
The impulse line is clogged.
Clean the impulse line.
The impulse line is leaky.
Seal the impulse line.
The impulse line is broken.
Replace the impulse line.
The impulse pressure is outside the adjustment range.
Set the shut-down pressure of the SAV.
The adjusting springs are not suitable for the application.
Replace the adjusting springs.
The SAV can be activated,
but not sealed.
The valve disc is damaged or worn out.
Replace the ASE or have it repaired by
DUNGS.
The valve seat is damaged.
Replace the valve seat.
The movable parts are contaminated with foreign particles.
Clean the movable parts or replace the ASE.
The drive is damaged.
Replace the ASE.
The O-ring is damaged.
Replace the O-ring or the ASE.
The SAV is leaking towards
the atmosphere.
The working diaphragm is damaged.
Change the working diaphragm or replace the
ASE.
The sealing ring between the ASE and the housing of the SAV is
damaged.
Replace the sealing ring or the ASE.
The O-ring in the ASE is damaged.
Replace the O-ring or the ASE.
• Repair work must only be performed by authorized and skilled personnel.
• Only use original spare parts.
4. Slowly open SAV, see section 11.3.
5. Once SAV has been opened completely, open the shutoff
valve on the outlet side.
3. Check if gas is available in the test section and release it
safely into the atmosphere.