background image

Domino

DFDALI

Mapping

DFDALI   module   is   shown   into   the  map   of   DCP   IDE   or 
BDTools like in the following figure. As for all 

Domino

 mod-

ules, the background of the module will be in green color if 
the module is connected and properly working, otherwise 
the background will be in red color.

The portion on the left side is related to the input section 
and it reports the diagnostic information and the brightness 
level   of   ballast   1   (text   box   on   the  bottom);   if   the  option 
“Regulation status” has been checked in the configuration 
panel, then this text box reports the automatic regulation 
status of the 8 zones (in decimal format to be interpreted in 
binary mode). 
The portion on the right side is related to the output section 
and it features two text boxes for entering the destination 
and command values.

Setting up

DCP IDE and BDTools allow to set the operating paramet-
ers of the DALI line during the system setting up and to 
perform some diagnostic functions. DFDALI module can be 
adapted  to any specific application. The setting up is per-
formed   via   the  

Domino

  bus   and   DFCP   (or   DFRS   or 

DFPRO) through a specific configuration panel that can be 
accessed from the menu of DCP IDE or BDTools.
From the menu, select Programming, Modules Configura-
tion and then DFDALI. The window shown in Figure 2 will 
be opened; the main parameters and options can be here 
defined as it will be described in the following of this para-
graph.
Before   to   proceed   with   any   action,   the   communication 
between the PC and, for instance, DFCP has to be opened. 
The top side of the configuration panel reports the section 
for the addresses management.
After having entered the address of the DFDALI to be man-
aged, it is possible to enable the input address of the mod-
ule through the check box named “Input Address” and then 
clicking on the button Program; by the button Read it is in-
stead possible to check the current setting.

It is also possible to activate the “Regulation Status” inform-
ation related to the 8 zones by checking the related option 
and   then   pressing   the   button   Program.   This   option,   of 
course, requires that the input section have been enabled.
Six tabs in the window allow some well defined functions as 
described in the following.
The button ID & Ver. on the lower side allows to read the 
firmware version of the selected DFDALI module.

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.1 May 2013

Page 5 of 11

HOME AND BUILDING AUTOMATION

Figure 2: Configuration panel – Addressing TAB

Содержание Domino DFDALI

Страница 1: ...ecalling of sceneries can be accomplished by the module The power supply needed for DFDALI module operation is derived from the Domino bus itself and from an auxiliary power supply for the DALI section Three fixed 2 way terminal block allow the connection of the module to the Domino bus to the auxiliary power sup ply and to the DALI bus Near to the Domino bus terminal block the module fea tures a ...

Страница 2: ... bus 1 output address and if enabled 1 input address The meaning of the data field of the two sections will be described in the following Input section On the input address if enabled 16 bits are available for the diagnostics of DALI system as described in the follow ing table Point Description 1 Current brightness or Regulation Status of the 8 zones 2 3 4 5 6 7 8 9 10 11 Polling disabled 12 Power...

Страница 3: ... HEX DEC 0x00 0x64 0 100 Set the brightness to 0 100 according to the current ramp 0x70 112 Disable polling 0x71 113 Enable polling 0x7D 125 Up command without one touch function 0x7E 126 Down command without one touch function 0x7F 127 Single command without one touch function 0x80 128 No operation in this case the value of the destination must be zero 0x87 135 Set the current brightness a MIN va...

Страница 4: ...easing of the buttons A similar example follows to send command to a group of ballasts V1 I1 1 I1 2 I1 3 AO2 P 0x8180 V1 P 0x817D I1 1 P 0x817E I1 2 P 0x8132 I1 3 The specified value at each variation will be transferred to the DALI devices assigned to group 1 At the releasing of each pushbutton the value is always set to 0x8180 no operation but needed to inform the module about the re leasing of ...

Страница 5: ...m the menu of DCP IDE or BDTools From the menu select Programming Modules Configura tion and then DFDALI The window shown in Figure 2 will be opened the main parameters and options can be here defined as it will be described in the following of this para graph Before to proceed with any action the communication between the PC and for instance DFCP has to be opened The top side of the configuration...

Страница 6: ...d to the line and for a single ballast Restoring of the settings does not imply the reset of the ballast address The visible result of the factory setting restoring is the switching on of the lamps at the bus failure default level that is typically 100 Mapping Once the ballasts have been random addressed it can be useful to reorder the assigned addresses thus simplifying the supervision and the ma...

Страница 7: ... 2 the bal lasts 1 3 and the group 3 the ballasts 2 4 5 The button Deselect remove all the X symbols on the grid The execution of the assignment of the groups clicking on the button Start will take in account only the ballast selec ted by the X symbol A timer icon will inform that the opera tion is running At the end of the procedure the normal mouse icon will be restored If the procedure has not ...

Страница 8: ...e to be recalled by ballasts during failure of Domino and or DALI bus Ramp the ramp value in seconds Preset writing a value 0 to 100 and clicking on the button on the right side the brightness will be forced to that value M1 M16 the value to be loaded into the 16 presets the button on the right side allows to recall the related preset stored into the ballast DUEMMEGI s r l Via Longhena 4 20139 MIL...

Страница 9: ...ontroller and any program ming To compile the table left click with the mouse on the first available cell on the Input column enter address and point without I or V with if needed and press Enter The command list will appear choose the desired function among Mono Up Down Recall Save the other two op tions are related to the automatic bright ness regulation see next paragraph The cell of the column...

Страница 10: ...to be sent to the ballasts In practice larger values of K increase the speed of the approaching to the set point Small values of K allow for greater stability of the regulation but a slower response while large values of K make the re sponse faster but some oscillations can appear Start Value is the value from which the regulation starts when it is activated The Auto options when checked place tha...

Страница 11: ...gulations of the relevant country The installation con figuration and programming of the devices must be carried out by trained personnel The installation and the wiring of the bus line and the related devices must be performed according to the recommendations of the manufacturers reported on the specific data sheet of the product and according to the applicable standards All the relevant safety r...

Отзывы: