Automatic brightness regulation

DFDALI module, starting from firmware version2.0, imple-
ments the automatic brightness regulation as function of a 
light sensor connected to the  

Domino

  bus (e.g. DFLUX). 

The TAB shown in Figure 8 allow to manage up to 8 zones 
(each one corresponding to a group in the range 1 to 8).
These functions are managed directly by DFDALI module, 
therefore no controller or specific programming is required.

To fill the table, double left click in the cell related to the 
zone to be set in the Sensor Address column, enter the ad-
dress of the light sensor (e.g. DFLUX module) for that zone 
and press Enter.  The cell related to Setpoint will be then 
automatically highlighted: enter the desired value and press 
Enter. The sequence is the same also for the next paramet-
ers: Hysteresis, T. Regulation, K and Start Value.

Setpoint  is the brightness level that  has to be kept. The 
regulation function works in order to keep the light value 
read from the sensor in the range (setpoint - hysteresis)  to 
(se hysteresis).

The regulation time, in seconds, is the interval with which 
the module compares the light level read by the sensor to 
the setpoint.

K is a parameter which, multiplied by the error (defined as 
the   difference   between   the   setpoint   and   the   brightness 
value measured by the sensor), defines the magnitude of 
the  increase  or  the  decrease,   in  respect  to  the  previous 
value, to be sent to the ballasts. In practice, larger values of 
K increase the speed of the approaching to the set point.

Small values of K allow for greater stability of the regulation 
but a slower response, while large values of K make the re-
sponse faster, but some oscillations can appear.
Start  Value is the value  from  which   the  regulation starts 
when it  is activated.

The Auto options, when checked, place that zone in auto-
matic regulation mode at the power up of the ballasts or of 
the 

Domino

 bus; if the option is not checked, the lights will 

go to the value set in the ballasts (typically 100 %).

Figure 8 shows some typical value for the just described 
parameters.

The buttons Start Prog. and Start Read. allow, respectively, 
to transfer the values currently shown in the table to DF-
DALI module and read the current configuration of DFDALI 
and report it into the table.
The buttons   From File and To File allow, respectively, to 
open a file, with .TRG extension, containing a previously 
saved regulation table and to save the table shown in the 
window to a file. The Default button clears the table.

To change the setpoint value of a group from a supervisor 
or similar devices, the destinations 0x91 

÷

 0x98 have to be 

used, as described in “Commands via bus” paragraph.

The functions 0xDD, 0xDE 0xDF allow to enable and dis-
able the automatic regulation from the bus on the group 
specified by the Destination field (0x81 

÷

 0x88)

DUEMMEGI

 s.r.l. - Via Longhena, 4 - 20139 MILANO

Tel. 02/57300377 - Fax 02/55213686 – 

www.duemmegi.it

Rel.: 2.1 May 2013

Page 10 of 11

HOME AND BUILDING AUTOMATION

Figure 8: Automatic brightness regulation

Содержание Domino DFDALI

Страница 1: ...ecalling of sceneries can be accomplished by the module The power supply needed for DFDALI module operation is derived from the Domino bus itself and from an auxiliary power supply for the DALI section Three fixed 2 way terminal block allow the connection of the module to the Domino bus to the auxiliary power sup ply and to the DALI bus Near to the Domino bus terminal block the module fea tures a ...

Страница 2: ... bus 1 output address and if enabled 1 input address The meaning of the data field of the two sections will be described in the following Input section On the input address if enabled 16 bits are available for the diagnostics of DALI system as described in the follow ing table Point Description 1 Current brightness or Regulation Status of the 8 zones 2 3 4 5 6 7 8 9 10 11 Polling disabled 12 Power...

Страница 3: ... HEX DEC 0x00 0x64 0 100 Set the brightness to 0 100 according to the current ramp 0x70 112 Disable polling 0x71 113 Enable polling 0x7D 125 Up command without one touch function 0x7E 126 Down command without one touch function 0x7F 127 Single command without one touch function 0x80 128 No operation in this case the value of the destination must be zero 0x87 135 Set the current brightness a MIN va...

Страница 4: ...easing of the buttons A similar example follows to send command to a group of ballasts V1 I1 1 I1 2 I1 3 AO2 P 0x8180 V1 P 0x817D I1 1 P 0x817E I1 2 P 0x8132 I1 3 The specified value at each variation will be transferred to the DALI devices assigned to group 1 At the releasing of each pushbutton the value is always set to 0x8180 no operation but needed to inform the module about the re leasing of ...

Страница 5: ...m the menu of DCP IDE or BDTools From the menu select Programming Modules Configura tion and then DFDALI The window shown in Figure 2 will be opened the main parameters and options can be here defined as it will be described in the following of this para graph Before to proceed with any action the communication between the PC and for instance DFCP has to be opened The top side of the configuration...

Страница 6: ...d to the line and for a single ballast Restoring of the settings does not imply the reset of the ballast address The visible result of the factory setting restoring is the switching on of the lamps at the bus failure default level that is typically 100 Mapping Once the ballasts have been random addressed it can be useful to reorder the assigned addresses thus simplifying the supervision and the ma...

Страница 7: ... 2 the bal lasts 1 3 and the group 3 the ballasts 2 4 5 The button Deselect remove all the X symbols on the grid The execution of the assignment of the groups clicking on the button Start will take in account only the ballast selec ted by the X symbol A timer icon will inform that the opera tion is running At the end of the procedure the normal mouse icon will be restored If the procedure has not ...

Страница 8: ...e to be recalled by ballasts during failure of Domino and or DALI bus Ramp the ramp value in seconds Preset writing a value 0 to 100 and clicking on the button on the right side the brightness will be forced to that value M1 M16 the value to be loaded into the 16 presets the button on the right side allows to recall the related preset stored into the ballast DUEMMEGI s r l Via Longhena 4 20139 MIL...

Страница 9: ...ontroller and any program ming To compile the table left click with the mouse on the first available cell on the Input column enter address and point without I or V with if needed and press Enter The command list will appear choose the desired function among Mono Up Down Recall Save the other two op tions are related to the automatic bright ness regulation see next paragraph The cell of the column...

Страница 10: ...to be sent to the ballasts In practice larger values of K increase the speed of the approaching to the set point Small values of K allow for greater stability of the regulation but a slower response while large values of K make the re sponse faster but some oscillations can appear Start Value is the value from which the regulation starts when it is activated The Auto options when checked place tha...

Страница 11: ...gulations of the relevant country The installation con figuration and programming of the devices must be carried out by trained personnel The installation and the wiring of the bus line and the related devices must be performed according to the recommendations of the manufacturers reported on the specific data sheet of the product and according to the applicable standards All the relevant safety r...

Отзывы: