20
2.8.3. Operation of this module on the host:
When the 32 channel fire linkage network module is added to the network public address system, first install and
connect the module well, and then modify the IP address of the module to be in the same network segment as the
host (refer to 5.8.2 equipment maintenance below); Then, set the parameters as shown in the figure below:.
If you need to modify the module IP address again, enter the corresponding IP in the browser, and then save to
modify successfully
2.8.4. Configuration of fire detection function
This module has the function of fire line fault detection. If you need to use this function, please read this section
carefully.
1. If you need to detect the line, 47K drop-down resistance box is needed to open the line detection channel.
2. On the side of this module, pull down the dial switch to open the master switch of line detection.
3. Input the IP address in the IE browser, and then enter into parameter configuration page and find the line
detection configuration, open the channel to use the new road detection function;
Alarm zones: shows all the
zones that included in the
current channel