e. Check wiring for proper routing and damage, such as
chaffing and/or cutting. Relocate and /or repair and
found damaged wires.
f. Check the torque of each battery connection for
70in/lbs.
CAUTION: DO NOT OVER TORQUE THESE CONNECTION AS SOME
BATTERIES HAVE LEAD POSTS AND THEY ARE VERY EASY TO
COMPRESS AND WILL CAUSE FAILURES IN THE FUTURE.
Note:
If Batteries are found to be leaking or fail the load test they should
be replaced. (Consult DSPM as to the status of your Battery Warranty)
2. Annual
CAUTION: BEFORE PERFORMING ANY OF THE FOLLOWING
STEPS BESURE THAT THE UPS/EMERGENCY LIGHTING INVERTER
HAS BEEN TUNED OFF.
i. Perform all Semi-annual Maintenance.
ii. Cabinet/Electronics
1. Inspect all power connections for loose connections.
Tighten any that are found loose. See the Torque table
below.
2. Check wiring for proper routing and damage, such as
chaffing and/or cutting. Relocate and /or repair and found
damaged wires.
3. Exercise all circuit breakers.
4. If there is a distribution internal to the cabinet and/or a panel
attached to the side of the UPS/Emergency Lighting Inverter,
check the power connections and exercise the breakers in
the cabinet.
iii. Batteries/Battery
Cabinet.
1. Check wiring for proper routing and damage, such as
chaffing and/or cutting. Relocate and /or repair and found
damaged wires.