SECTION 3 – INSTALLATION
The ETERNALIGHT 1 UPS system is shipped on a pallet with the batteries outside
the UPS. This Manual, battery jumper wires and accessories may be included within
the packaging, ensure that these are not discarded with the packaging. Unwrap the
UPS and carefully inspect the external surfaces for abrasions, indentations, or other
obvious damage.
File a claim with the shipping agency for any damage caused by shipping. Forward a
copy of the damage claim to DSPM.
Mount the UPS system so each side and the top has six inches of clearance for
airflow. Leave appropriate space in the front so the front door can be opened fully for
operation and installation.
3-1 INSTALLATION EQUIPMENT
The following instructions cover general requirements for standard installation of the
input and output power circuits, battery connections and control interface
connections. Install the UPS using the procedures in this section. Care must be
taken to insure the unit is properly connected. Connections should be torque as
shown in Table 2-1
TABLE 2-1
WIRING TERMINAL TORQUE