SECTION 2 – PREINSTALLATION
2-1 SITE PLANNING AND PREPARARTION
The ETERNALIGHT 1 is designed for installation indoors where it is protected from the
elements. The UPS can be installed in a variety of different environments including
computer rooms, offices, and industrial/process control locations. For the best
performance and reliability, temperature extremes should be avoided.
Listed below are the environmental specifications for the ETERNALIGHT 1 UPS
SYSTEM.
Adequate clearance around the equipment should be provided for service access and
proper equipment cooling. The UPS must be protected from contact with water and
other liquids. If the UPS is installed in a small, enclosed area, provisions for additional
cooling may be necessary.
OPERATING ENVIRONMENT.
Provide an operating environment that meets the
following conditions:
o
AMBIENT TEMPERATURE 32
°
to 104
°
F
0
°
to 40
°
C
o
OPERATING ALTITUDE 2,286 M (7500 FT)
o
NON-OPERATING ALTITUDE up to 3,048 M (10,000 FT)
o
RELATIVE HUMIDITY
0% to 95% (non-condensing)
Operating the UPS and batteries at either extreme of the temperature range may affect
the long-term reliability of the system. This is especially true of the sealed,
maintenance-free batteries. Sealed, maintenance-free batteries are designed to operate
at normal room temperatures (72 to 77
°
F)
! WARNING ! BATTERY SHELF LIFE !
•
BATTERY SHELF LIFE, WHEN STORED UNDER TEMERATURE CONDITIONS of
66
°
F ~ 77
°
F, is FOUR (4) MONTHS MAXIMUM AFTER THE SHIP DATE.
•
BATTERY MUST BE RECHARGED FOR EIGHT HOURS AFTER THIS DATE
OTHERWISE THEY MAY BE DAMAGED.