User’s Manual 

 
 
 
 
 

 
Eternalight 1 
Uninterruptible Power System 
 
 
 
 
Technical Manual 

#018-0056-03 Revision G

 

Содержание Eternalight 1

Страница 1: ...Service 714 970 2304 m f 8 00 5 00 after hours 951 840 0811 Web Page www DSPManufacturing com Email sales dspmanufacturing com 1 D S P M Inc User s Manual Eternalight 1 Uninterruptible Power System Technical Manual 018 0056 03 Revision G ...

Страница 2: ...Uninterruptible Power Systems UPS Power Conditioners Frequency Converters and Specialty Transformers Since our beginnings DSPM has shipped many of these fine products to discerning customers for use on sensitive equipment and critical loads HEADQUARTERS DSPM Inc 1921 S Quaker Ridge Place Ontario Ca 91761 SALES Phone 714 970 2304 Fax No 714 970 6171 www DSPManufacturing com Email sales dspmanufactu...

Страница 3: ...TION This document contains proprietary and confidential information of DSPM Inc DSPM In consideration of the receipt of this document the recipient agrees not to copy any of its contents nor disclose them to or allow them to be used by any person not currently a DSPM employee or an employee of the recipient having a need to know without the express written consent of DSPM and further agrees to su...

Страница 4: ... SAFETY When using Electrical Equipment basic safety precautions should always be followed including the following IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1 Do not mount near gas or electric heaters 2 Check that all electrical connections are tightened properly 3 Equipment should be mounted in a location to prevent tampering by unauthorized personal 4 Equipment should be locke...

Страница 5: ...cautions should perform servicing of batteries 2 Do not dispose of batteries in a fire The battery may explode 3 Do not open and manipulate the battery 4 A battery can present a risk of electrical shock and high short circuit current Remove watches rings or any other metal objects Use only insulated tools 5 Install in a protected environment 6 Always turn off the battery circuit breaker before tes...

Страница 6: ...supply The critical load receives only clean sine wave power at all times There are no disturbances or power interruptions on the output when the UPS transfers to battery operation Transfers to and from battery operations are No Break transfers The internal maintenance free batteries provide a few minutes to hours depending upon model of backup power Upon restoration of input power the UPS automat...

Страница 7: ...es Electrical disturbances can come from practically anywhere from the incoming power lines and from within a building Outside electrical disturbances include lightning strikes utility switching brownouts and accidents Electrical disturbances from within the building can be caused by load cycling elevators HVAC systems fault conditions welders and other electrically noisy equipment Whether the ele...

Страница 8: ...Phone 714 970 2304 Fax 714 970 6171 Service 714 970 2304 m f 8 00 5 00 after hours 951 840 0811 Web Page www DSPManufacturing com Email sales dspmanufacturing com 8 Typical Front View Doors Closed ...

Страница 9: ...Phone 714 970 2304 Fax 714 970 6171 Service 714 970 2304 m f 8 00 5 00 after hours 951 840 0811 Web Page www DSPManufacturing com Email sales dspmanufacturing com 9 Typical left hand view ...

Страница 10: ...Phone 714 970 2304 Fax 714 970 6171 Service 714 970 2304 m f 8 00 5 00 after hours 951 840 0811 Web Page www DSPManufacturing com Email sales dspmanufacturing com 10 Typical right hand view ...

Страница 11: ...or correction This greatly reduces the amount of current demanded from your building wiring system yielding a highly efficient Building Friendly UPS System RECTIFIER INVERTER The Rectifier Inverter system provides controlled sine wave power to the output The output voltage and frequency are monitored by the microprocessor and controlled to provide precision power with changing inputs and outputs t...

Страница 12: ...st be protected from contact with water and other liquids If the UPS is installed in a small enclosed area provisions for additional cooling may be necessary OPERATING ENVIRONMENT Provide an operating environment that meets the following conditions o AMBIENT TEMPERATURE 32 to 104 F 0 to 40 C o OPERATING ALTITUDE 2 286 M 7500 FT o NON OPERATING ALTITUDE up to 3 048 M 10 000 FT o RELATIVE HUMIDITY 0...

Страница 13: ... 1 240 29 1 240 52 0 208 277 68 25 2 208 277 121 45 1 120 58 3 120 104 1 240 29 1 240 52 0 240 277 59 25 2 240 277 105 45 1 120 58 3 120 104 1 240 29 1 240 52 0 277 277 51 25 2 277 277 91 45 1 120 58 3 120 104 1 240 29 1 240 52 0 277 25 2 277 45 1 7 480 480 30 14 5 12 5 480 480 53 26 0 120 75 0 120 125 0 240 37 5 240 62 5 120 277 150 32 4 120 277 250 54 1 120 75 0 120 125 0 240 37 5 240 62 5 208 2...

Страница 14: ...vious damage File a claim with the shipping agency for any damage caused by shipping Forward a copy of the damage claim to DSPM Mount the UPS system so each side and the top has six inches of clearance for airflow Leave appropriate space in the front so the front door can be opened fully for operation and installation 3 1 INSTALLATION EQUIPMENT The following instructions cover general requirements...

Страница 15: ...t wire size required An insulated grounding conductor must be installed as part of the input circuit Size the grounding conductor in accordance with NEC and local codes The manufacturer recommends a parity sized ground with respect to the input power wires 3 1 INSTALLATION OF EQUIPMENT continued The UPS is designed to provide superior isolation and protection for sensitive loads The UPS can be wir...

Страница 16: ...late matches the customer supplied voltage If the voltage does not match STOP installation of the UPS and contact Customer Service at DSPM 2 Verify that Input cable and conduit are routed correctly and are in position to connect the unit 3 Open front doors of UPS 4 Select desired mounting hole and remove knockout 5 Pass wires through the mounting hole 6 Secure conduit fitting to the panel of unit ...

Страница 17: ...s not exceed unit capacity If the voltage does not match or the intended applied load exceeds unit capacity STOP installation of the UPS and contact Customer Service at DSPM 2 Verify that Output cable s and conduit s are routed correctly and are in position to connect the unit 3 Open front doors of UPS 4 Select desired mounting hole s and remove knockout 5 Pass wires through the mounting hole 6 Se...

Страница 18: ...ms connect the batteries in series i e plus terminal to minus terminal from one battery to another battery The battery circuit breaker must be off during the installation Install the batteries and connect the battery cables Connect the minus terminal of the battery group to the battery circuit breaker terminal that is labeled Connect the positive terminal of the battery group to the battery circui...

Страница 19: ...r and note the D C voltage at the battery circuit breaker The voltage must be the correct polarity positive lead of the meter to the positive terminal of the circuit breaker 4 The D C voltage should read between 220 to 240 VDC for an 18 battery unit and 118 to 130 for a 10 battery unit If the D C voltage reads below 210 volts D C or 115 volts DC this means the battery cables are not connected corr...

Страница 20: ...rcuit breaker is OFF 2 Check all output circuit breaker s optional are OFF 3 Check the battery circuit breaker s are OFF 4 Energize the Utility feeder to the unit 5 Turn the Input circuit breaker ON 6 Wait for the System display message instructing you to close the battery breaker 7 Turn on the Battery Breaker 8 Wait for the System Display message stating unit is operational 9 Turn on the Output B...

Страница 21: ... sequence fault has not been corrected and system has timed out 13 Invrtr FLT a hardware fault has been detected by the inverter control board IGBT PCBA caused by IGBT failure unexpected power on reset or DC Bus over voltage 14 DC Bus OV DC Bus has gone over fault limit 15 DC Bus UV DC Bus has gone below fault limit 16 Input OFrq Input frequency has gone over fault limit 17 Input UFrq Input freque...

Страница 22: ...tem 51 RunState1 Initial system checks complete awaiting DC breaker closure 52 RunState2 Startup complete system ready 53 RunState3 Utility power failure system is on a battery run 54 Bypass on System is in bypass 56 Battry Low Battery Voltage is low causes a system shutdown 57 KeyCode OK Key Code Accepted 58 AirFlow DN AirFlow fault detected DC BUS set to minimum value CAUTION Verify that the out...

Страница 23: ...mally on circuits can be provided These circuits are on when AC input power is on and turned off to lower the load requirements where input AC power fails 2 Normally off circuits can be provided These circuits provide power only when the UPS system is on battery power These circuits usually power exits signs and lighting 5 0 TECHNICAL SUPPORT 1 For Technical Support or any questions not covered in...

Страница 24: ...ronics 1 Inspect all fans and insure proper operation ii Batteries Battery Cabinet 1 Inspect the battery cases for leakage 2 Perform a battery load test of each individual battery a Turn off the Battery Breaker b Using a Battery load tester connected to only one battery test the battery and record the battery voltage after a 5 to 10 second load test The picture to the left is an example of the typ...

Страница 25: ...Battery Warranty 2 Annual CAUTION BEFORE PERFORMING ANY OF THE FOLLOWING STEPS BESURE THAT THE UPS EMERGENCY LIGHTING INVERTER HAS BEEN TUNED OFF i Perform all Semi annual Maintenance ii Cabinet Electronics 1 Inspect all power connections for loose connections Tighten any that are found loose See the Torque table below 2 Check wiring for proper routing and damage such as chaffing and or cutting Re...

Страница 26: ...ION AS SOME BATTERIES HAVE LEAD POSTS AND THEY ARE VERY EASY TO COMPRESS AND WILL CAUSE FAILURES IN THE FUTURE Note If Batteries are found to be leaking or fail the load test they should be replaced Consult DSPM as to the status of your Battery Warranty 7 0 TROUBLE SHOOTING 7 0 1 If unable to resolve any problem please contact DSPM for assistance DSPM Inc 1921 South Quaker Ridge Place Ontario CA 9...