Three Phase Emergency Lighting Inverter User’s Manual
#018-7002-00
Table 1
2.1. POWER RATING
Three to one-hundred and twenty-five Kilowatt (or 3,000 Watts - 125,000 Watts) three phase output unit
uses the latest DSP/PWM technology to provide the most advanced performance and reliability features.
2.2. INPUT
208Y/120, 480Y/277, 208 or 480VAC input 60Hz
2.3. OUTPUT
208Y/120 or 480Y/277VAC True “on-line” design is ≥99% efficient at 100% linear load
2.4. BATTERIES
2.4.1.
Sealed, maintenance-free, lead calcium (AGM) batteries
2.4.2.
10-Year prorated warranty
2.4.3.
DSP/PWM Smart Battery Monitoring System
is
TEMPERATURE COMPENSATED
maintaining
maximum runtime and battery life
2.4.4.
Microprocessor controlled recharge and DSP/PWM overcharge protection standard
2.5. LAMPS AND LOADS
2.5.1.
Emergency power provides
FULL LIGHT OUTPUT
from all lamps and fixtures for the entire run-
time
2.5.2.
Operates fluorescent, compact fluorescent, incandescent, quartz, H.I.D., LED and other lamp types
2.5.3.
Standard or electronic ballasts, dimming devices or panels, sensors and most control equipment
2.5.4.
Standard or LED Exits and other safety equipment
2.6. CODES
2.6.1.
Listed to UL 924, meets NFPA 101, NFPA 70, NEC and OSHA standards
2.6.2.
Cities of Chicago and New York approved
2.6.3.
Complies with the Buy American Act
2.7. PROTECTION
2.7.1.
Provides overload, surge and undercurrent protection using DSP/PWM technology and DSPM
Watchdog Software
to protect system performance and reliability
2.7.2.
Surge protection against load surges as defined in ANSI/IEEE C62.45 category A and B
2. SPECIFICATIONS
The Three Phase Inverter maintains efficient AC Emergency Power to operate all emergency lighting fixtures
at “full-light” output, providing superior dependability and security to commercial/industrial environments in a
small footprint.
The UPS System Label displays the rated kW as well as nominal voltages. There are System
Labels located on the interior side of the UPS front door and the exterior side of the unit.
3
Φ
Power
Rating
UPS
Battery
Weight British
Battery
Type
Voltage
(VAC)
Output
Safety
Series
Cabinet
Cabinet
(Com-
Thermal
Protec-
tion
Approv-
als
Dimensions
Dimensions
bined)
Unit
KVA/KW W
H
D
W
H
D
(lbs)
BTU’s
Sealed,
Input Output Input and
UL924
3.0
42”
71” 22.5”
Not required
980
816
Maintenance Select Select
Output
UL1778
4.5
42”
71” 22.5”
Not required
1100 1224
Free (AGM)
120,
120,
Circuit
NFPA 101
(Consult
6.0
42”
71” 22.5”
Not required
1350 1632
Lead
208,
208,
Breakers
NFPA 70
Factory
8.0
42”
71” 22.5” 42”
71” 22.5”
1700 2176
Calcium
240,
277,
standard
NEC
For others) 10.0
42”
71” 22.5” 42”
71” 22.5”
2250 2720
277,
480,
12.0
42”
71” 22.5” 42”
71” 22.5”
2700 3264
Or
120/240
16.0
42”
71” 22.5” 42”
71” 22.5”
2950 4352
480
Or
20.0
42”
71” 22.5” 42”
71” 22.5”
3800 5440
120/277
24.0
42”
71” 22.5” 42”
71” 22.5”
4350
652
30.0
42”
71” 22.5” 42”
71” 22.5”
5150 8160
40.0
42”
71” 22.5” 42”
71” 22.5”
6790 10880
50.0
42”
71” 22.5” 42”
71” 22.5”
8384 13600
60.0
50”
71” 22.5”
Consult Factory
16320
80.0
50”
71” 22.5”
Consult Factory
21760
100.0
50”
71” 22.5”
Consult Factory
27200
125.0
50”
71” 22.5”
34000
Consult Factory