Description of Controls
057-276 ISSUE: 1.3
Page 38 of 74
Icon
Description
Open Generator
The
Open Generator
button controls the operation of the generator load
switch and is only active in
Manual Mode
once the generator bus is
available.
Synchronising NOT Enabled:
Pressing the
Open Generator
button when
the generator is available and on load causes the generator load switch to open
(‘Close Generator’ becomes inactive)
. Further presses of the
Open Generator
button have no effect.
Synchronising Enabled:
Pressing the
Open Generator Breaker
button
when the generator is available and on load causes the generator to ramp down
if possible and open the breaker
(‘Close Generator’ becomes inactive)
. Further
presses of the
Open Generator Breaker
button have no effect.
Close Generator
The
Close Generator
button control the operation of the generator load
switch and is only active in
Manual Mode
once the generator bus is
available.
Synchronising NOT Enabled:
Pressing the
Close Generator
button when
the generator is available and off load causes the generator load switch to close
(‘Close Generator’ becomes active)
. Further presses of the
Close Generator
button have no effect.
Synchronising Enabled:
Pressing the
Close Generator
button when the
generator is available and of load causes the generator to synchronise if required
and then closes the generator load switch
(‘Close Generator’ becomes active)
.
Further presses of the
Close Generator
button have no effect.
Содержание DSE8003 MKII