Description of Controls
Page 41 of 74
057-276 ISSUE: 1.3
Icon
Description
Transfer to Mains
The
Transfer to Mains
button control the operation of the mains load
switching and is only active in
Manual Mode
once the generator bus is
available.
‘Normal’ Breaker Button Control
•
Synchronising NOT Enabled:
Pressing the
Transfer to Mains
button when the Mains is available and off load, the generator bus load
switch is opened
(‘Close Bus’ becomes inactive)
and the mains load
switch is closed
(‘Close Mains’ becomes active)
. Further presses of the
Transfer to Mains
button have no effect.
•
Synchronising Enabled:
Pressing the
Transfer to Mains
button
when the Mains is available and off load, the module synchronise the
Generator Bus to the Mains. The mains load switch is then closed in
parallel with the Generator Bus
(‘Close Mains’ & ‘Close Bus’ are
active)
. Further presses of the
Transfer to Mains
button ramps the
entire load from the Generator Bus to the Mains. Once done, the
Generator Bus load switch opens
(‘Close Bus’ becomes inactive)
leaving just the mains supplying the load.
‘Alternative’ Breaker Button Control
•
Synchronising NOT Enabled:
Pressing the
Transfer to Mains
button when the Mains is available and off load, the generator bus load
switch is opened
(‘Close Bus’ becomes inactive)
and the mains load
switch is closed
(‘Close Mains’ becomes active)
. Further presses of the
Transfer to Mains
button opens and closes the mains load switch
(‘Close Mains’ changes state)
and leaves the bus load switch in the
open position
(‘Close Bus’ remains inactive)
.
•
Synchronising is enabled:
Pressing the
Transfer to Mains
button
when the Mains is available and off load, the module synchronise the
Generator Bus to the Mains. The mains load switch is then closed in
parallel with the Generator Bus
(‘Close Mains’ & ‘Close Bus’ are
active)
. Further presses of the
Transfer to Mains
button ramps the
entire load from the Mains to the Generator Bus. Once done, the Mains
load switch opens
(‘Close Mains’ becomes inactive)
leaving just the
Generator Bus supplying the load.