Specification
Page 19 of 74
057-276 ISSUE: 1.3
2.7 SOUNDER
The module features an internal sounder to draw attention to warning, shutdown and electrical trip
alarms.
Description
Specification
Sounder Level
64 db at 1 m
2.7.1 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION
Should an external alarm or indicator be required, this can be achieved by using the DSE8003 MKII
running editor to configure an auxiliary output for “Audible Alarm”. See section entitled
Front Panel
Configuration
for further details.
The audible alarm output activates and de-
activates at the same time as the module’s internal
sounder. The monitored DSE controllers alarm mute input and
alarm mute button activate ‘in parallel’
with each other. Either signal will mute both the internal sounder and audible alarm output.