DSE871x mono remote display
Part No. 057-129 DSE871x mono remote display ISSUE 2.1 21/09/2010 ADM
7
2 INTRODUCTION
This document details the installation and operation requirements of the DSE871x series mono display modules,
part of the DSEPower® range of products.
The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or
supplied to another party, ensure that this document is passed to them for reference purposes.
This is not a controlled document. You will not be automatically informed of updates. Any future updates of this
document will be included on the DSE website at www.deepseaplc.com
DSE871x display module is used in conjunction with DSE87xx controller. The DSE871x display is NOT a
standalone module.
The DSE871x series is designed to provide differing levels of functionality across a common platform. This allows
the generator OEM greater flexibility in the choice of controller to use for a specific application.
The DSE871x series module has been designed to allow the operator to start and stop the generator, and if
required, transfer the load to the generator either manually (via fascia mounted push buttons) or automatically.
Synchronising and Load Sharing features are included within the controller, along with the necessary protections for
such a system.
The user also has the facility to view the system operating parameters via the LCD display.
The DSE87xx module monitors the engine, indicating the operational status and fault conditions, automatically
shutting down the engine and giving a true first up fault condition of an engine failure by a COMMON AUDIBLE
ALARM. The LCD display indicates the fault.
The powerful microprocessor contained within the module allows for incorporation of a range of enhanced features:
•
Text based LCD display (supporting multiple languages).
•
True RMS Voltage, Current and Power monitoring.
•
Engine parameter monitoring.
•
Fully configurable inputs for use as alarms or a range of different functions.
•
Engine ECU interface to electronic engines.
•
Direct connection to governor / AVR for synchronising and load sharing
•
R.O.C.O.F. and Vector shift for detection of mains failure when in parallel with the mains supply.
Using a PC and the Configuration Suite software allows alteration of selected operational sequences, timers and
alarms.
Additionally, the module’s integral fascia configuration editor allows adjustment of a subset of this information.
A robust plastic case designed for front panel mounting houses the module. Connections are via locking plug and
sockets.