Installation – Description Of Controls
20
Part No. 057-129 DSE871x mono remote display ISSUE 2.1 21/09/2010 ADM
4.2 DESCRIPTION OF CONTROLS
The following section details the function and meaning of the various controls on the module.
4.3 DSE8711 DISPLAY FOR DSE8710 AUTOSTART
NOTE:- “Generator on load” LED has two modes of operation depending upon the configuration of the
controllers digital inputs.
1) Digital input configured for “Generator closed auxiliary” – The LED illuminates when the generator
closed auxiliary input is active – The LED shows the state of the auxiliary contact.
2) There is NO input configured for “Generator closed auxiliary” (factory default setting) – The LED
illuminates when the DSE8710 gives the loading signal to the generator – The LED shows the state of
the DSE8710s loading request.
Menu navigation
buttons
Four configurable
LEDs
Select Stop
mode
Select Manual
mode
Select
Auto
mode
Mute
alarm /
Lamp
test
Start
engine
(when in
manual
mode)
Close
generator
(manual mode
only)
Open
generator
(manual mode
only)
Main status and
instrumentation display
Close Generator LED.
On When The Generator
Is Required To Be On
Load.
Generator Available
LED.
On when the
generator is within
limits and able to
take load.