Protections
Part No. 057-129 DSE871x mono remote display ISSUE 2.1 21/09/2010 ADM
55
6.9 ROCOF / VECTOR SHIFT
When configured to run in parallel with the mains (utility) supply, the module monitors for ROCOF / Vector shift trips
according to the module’s configuration settings. This is included within the module and will detect failure of the
mains supply during parallel operation with the generator.
NOTE:
NOTE:
NOTE:
NOTE:---- This protection operates only when in parallel with the mains supply and is disabled at all
This protection operates only when in parallel with the mains supply and is disabled at all
This protection operates only when in parallel with the mains supply and is disabled at all
This protection operates only when in parallel with the mains supply and is disabled at all
other times.
other times.
other times.
other times.
Should either of these alarms operate, the module will perform a controlled shutdown (electrical trip) of the
generator. This operation must be manually reset :
1) Press
button. The engine will stop if it is still running and the alarm is cleared.
2) Activate digital input configured to “Clear ROCOF/Vector shift” if this has been provided.
3) Press
and
button together and hold for 5 seconds. The ROCOF/Vector shift instrument is displayed
and all ‘peak hold’ values are reset, clearing the ROCOF/Vector shift alarm.
For details on activating and configuring the ROCOF/Vector shift protection, you are referred to the 8700
configuration software manual.