Operation
93
6.5.3 GENERATOR BUS AVAILABLE
Once the generator closes its load switch, the generator bus is seen as available and the generator
bus LED illuminates.
In
Auto Mode
, the generator load switch is closed automatically (if instructed too) when the
generator bus is seen as available, synchronising to the Mains if required. A loading request can
come from a number of sources:
•
Failure of mains supply
•
High mains load (when the module is configured for an automatic peak lopping system)
•
Activation of an auxiliary input that has been configured to
Remote Start On Load
or
Remote
Start In Island Mode
function
.
•
Activation of an auxiliary input that has been configured to
Auxiliary Mains Failure.
•
Activation of the inbuilt exercise scheduler if configured for ‘Parallel’ or ‘Island’ operation.
•
Instruction from external remote telemetry devices using the RS232, RS485 or Ethernet
interface.
Load ramping takes place when appropriate, the DSE8661 controls the generator bus to provide the
configured power to the load and or mains supply.
6.5.3.1
BUS MODE
In this mode, the generator bus is used to provide a
Fixed
amount of active power (kW). This is set
using the DSE Configuration Suite Software in SCADA | Bus | MSC Link |
Load Parallel Power
parameter.
How much reactive power provided depends upon the kV Ar or pf selection:
•
kV Ar – The generator bus provides the number of kV Ar set in the
Load Parallel V Ar
parameter. The power factor is variable in order to achieve this.
•
pf – The generator bus produces power at the power factor set in the
Load Power Factor
parameter. The kV Ar is variable in order to achieve this.
If all start requests are removed, the
Stopping Sequence
begins.
6.5.3.2
MAINS MODE
In this mode, the generator bus is used to provide a
Variable
amount of active power (kW), to
maintain the mains import or export levels at the configured values. This is set using the DSE
Configuration Suite Software in SCADA | Bus | MSC Link |
Load Parallel Power
parameter.
How much reactive power is taken from or exported to the mains depends upon the kV Ar or pf
selection:
•
kV Ar – The generator bus is used to provide a fxied amount of kV Ar to maintain the mains
import or export V Ar at the level set in the
Load Parallel V Ar
parameter. The mains power
factor is variable in order to achieve this.
•
pf – The generator bus is used to provide enough kV Ar to maintain the mains import or
export at the power factor configured into the
Load Power Factor
parameter. The mains kV
Ar is variable in order to achieve this.
As the load increases and decreases, generators on the generator bus may start and stop
automatically depending upon their configuration.
If all start requests are removed, the
Stopping Sequence
begins.
Содержание DSE8661
Страница 11: ...Specification 11...
Страница 52: ...Installation 52 4 2 1 TYPICAL SYSTEM DIAGRAM NOTE The DSE8661 module does NOT support multiple mains systems...
Страница 53: ...Installation 53 4 2 2 TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE STAR 4 2 2 1 MODULE INTER CONNECTION RS485 TO RS485...
Страница 54: ...Installation 54 4 2 2 2 MODULE INTER CONNECTION DSENET TO RS485...
Страница 55: ...Installation 55 4 2 3 ALTERNATE TOPOLOGIES 4 2 3 1 SINGLE PHASE 2 WIRE...
Страница 56: ...Installation 56 4 2 3 2 2 PHASE L1 L2 3 WIRE DELTA...
Страница 57: ...Installation 57 4 2 3 3 2 PHASE L1 L3 3 WIRE DELTA...
Страница 58: ...Installation 58 4 2 3 4 3 PHASE 3 WIRE DELTA...
Страница 59: ...Installation 59 4 2 3 5 3 PHASE 4 WIRE DELTA...
Страница 84: ...Operation 84 6 1 2 STOPPING THE GENERATOR Select Stop Reset mode The generator is requested to stop...
Страница 97: ...Operation 97 6 7 MULTIPLE MAINS OPERATION NOTE The DSE8661 module does NOT support multiple mains systems...
Страница 120: ...This Page is Intentionally Left Blank 120...