Operation
91
6.4.3 UNLOADING GENERATOR BUS
The generator bus load switch is not automatically opened. To manually open the generator bus load
switch:
•
Press the
Manual
Mode
button followed by the
Transfer to Mains
button
•
Press the
Auto Mode
button. The module observes all
Auto Mode
start requests
and stopping timers before beginning the
Auto Mode Stopping Sequence
.
•
Press the
Stop/Reset Mode
button to open the generator bus load switch and remove
start request on MSC link.
•
Activation of an auxiliary input that has been configured to
Bus Load Inhibit
6.4.4 STOPPING SEQUENCE
In
Test
Mode
the set continues to run until either:
•
The
Stop/Reset Mode
button is pressed – The generator bus load switch opens
immediately and start request on MSC link is removed.
•
The
Auto Mode
button
is pressed. The module observes all
Auto Mode
start
requests and stopping timers before beginning the
Auto Mode Stopping Sequence
.
Содержание DSE8661
Страница 11: ...Specification 11...
Страница 52: ...Installation 52 4 2 1 TYPICAL SYSTEM DIAGRAM NOTE The DSE8661 module does NOT support multiple mains systems...
Страница 53: ...Installation 53 4 2 2 TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE STAR 4 2 2 1 MODULE INTER CONNECTION RS485 TO RS485...
Страница 54: ...Installation 54 4 2 2 2 MODULE INTER CONNECTION DSENET TO RS485...
Страница 55: ...Installation 55 4 2 3 ALTERNATE TOPOLOGIES 4 2 3 1 SINGLE PHASE 2 WIRE...
Страница 56: ...Installation 56 4 2 3 2 2 PHASE L1 L2 3 WIRE DELTA...
Страница 57: ...Installation 57 4 2 3 3 2 PHASE L1 L3 3 WIRE DELTA...
Страница 58: ...Installation 58 4 2 3 4 3 PHASE 3 WIRE DELTA...
Страница 59: ...Installation 59 4 2 3 5 3 PHASE 4 WIRE DELTA...
Страница 84: ...Operation 84 6 1 2 STOPPING THE GENERATOR Select Stop Reset mode The generator is requested to stop...
Страница 97: ...Operation 97 6 7 MULTIPLE MAINS OPERATION NOTE The DSE8661 module does NOT support multiple mains systems...
Страница 120: ...This Page is Intentionally Left Blank 120...