Installation
61
4.3 TYPICAL ARRANGEMENT OF DSENET®
CAUTION!: The DSE8661 modules MUST NOT be connected together using only the
DSENet® Port on each module as it is not isolated.
NOTE: For further details on connection between the DSE8661 modules using DSENet®,
see the section entitled
DSE8661 (DSENet
®
to RS485) Typical Wiring Diagram
elsewhere in
this document.
NOTE: For further details of module configuration, refer to DSE Publication:
057-215
DSE8661 Configuration Suite Software Manual.
NOTE: A maximum of 20 DSENet® expansion modules can be connected to the DSE host
module, made up of the following devices :
Module
Maximum Number Supported
DSE2130 Input Expansion
4
DSE2131 Ratiometric Input Expansion
4
DSE2133 RTD/Thermocouple Intput Expansion
4
DSE2152 Analogue Output Expansion
4
DSE2157 Relay Output Expansion
10
DSE2548 LED Expansion
10
Содержание DSE8661
Страница 11: ...Specification 11...
Страница 52: ...Installation 52 4 2 1 TYPICAL SYSTEM DIAGRAM NOTE The DSE8661 module does NOT support multiple mains systems...
Страница 53: ...Installation 53 4 2 2 TYPICAL WIRING DIAGRAM 3 PHASE 4 WIRE STAR 4 2 2 1 MODULE INTER CONNECTION RS485 TO RS485...
Страница 54: ...Installation 54 4 2 2 2 MODULE INTER CONNECTION DSENET TO RS485...
Страница 55: ...Installation 55 4 2 3 ALTERNATE TOPOLOGIES 4 2 3 1 SINGLE PHASE 2 WIRE...
Страница 56: ...Installation 56 4 2 3 2 2 PHASE L1 L2 3 WIRE DELTA...
Страница 57: ...Installation 57 4 2 3 3 2 PHASE L1 L3 3 WIRE DELTA...
Страница 58: ...Installation 58 4 2 3 4 3 PHASE 3 WIRE DELTA...
Страница 59: ...Installation 59 4 2 3 5 3 PHASE 4 WIRE DELTA...
Страница 84: ...Operation 84 6 1 2 STOPPING THE GENERATOR Select Stop Reset mode The generator is requested to stop...
Страница 97: ...Operation 97 6 7 MULTIPLE MAINS OPERATION NOTE The DSE8661 module does NOT support multiple mains systems...
Страница 120: ...This Page is Intentionally Left Blank 120...