DSE7200 / 7300 Series Operators Manual
34
4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
22
Magnetic pickup Positive
0.5mm²
AWG 20
Connect to Magnetic Pickup device
23
Magnetic pickup Negative
0.5mm²
AWG 20
Connect to Magnetic Pickup device
24
Magnetic pickup screen
Shield
Connect to ground at one end only
25
CAN port H
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
26
CAN port L
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
27
CAN port Common
0.5mm²
AWG 20
Use only 120
Ω
CAN approved cable
28
+
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
29
-
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
30
SCR
0.5mm²
AWG 20
Use only 120
Ω
RS485 approved cable
NOTE:- Terminals 31 to 38 are not fitted to the 7200 / 7300 controller
NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is
earthed at one end ONLY.
NOTE:- Screened 120
Ω
Ω
Ω
Ω
impedance cable specified for use with CAN must be used for the CAN link
and the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120
Ω
Ω
Ω
Ω
impedance cable suitable for CAN
use (DSE part number 016-030)
NOTE:- When the module is configured for CAN operation, terminals 22, 23 & 24 should be left
unconnected. Engine speed is transmitted to the 7000 series controller on the CAN link.
Refer to
Electronic Engines and DSE Wiring
for further information. Part No. 057-004.
Содержание DSE7210
Страница 41: ...DSE7200 7300 Series Operators Manual 41 4 3 1 7210 AUTOSTART CONTROLLER 3 phase 4 wire...
Страница 42: ...DSE7200 7300 Series Operators Manual 42 4 3 2 7220 AMF CONTROLLER 3 phase 4 wire...
Страница 121: ...This page is intentionally blank 121...
Страница 122: ...This page is intentionally blank 122...
Страница 128: ...DSECONTROL Gu a de Utilizaci n R pida DSE7000 057 101 Autor John Ruddock...